AIR COOLED
CONDENSING UNITS
92-104921-09-07 (5/16)
Printed in USA
[ ] indicates metric conversions.
Do not destroy this manual.
Please read carefully
and keep in a safe place
for future reference by a
serviceman.
WARNING
THESE INSTRUCTIONS
ARE INTENDED AS AN AID
TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR
PROPER INSTALLATION,
ADJUSTMENT, AND
OPERATION OF THIS
UNIT. READ THESE
INSTRUCTIONS
THOROUGHLY
BEFORE ATTEMPTING
INSTALLATION OR
OPERATION. FAILURE
TO FOLLOW THESE
INSTRUCTIONS MAY
RESULT IN IMPROPER
INSTALLATION,
ADJUSTMENT, SERVICE,
OR MAINTENANCE
POSSIBLY RESULTING IN
FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE,
PERSONAL INJURY, OR
DEATH.
INSTALLATION INSTRUCTIONS
(-)A13, (-)A14 & (-)A16 MODEL SERIES –
13, 14 & 16 SEER
WARNING:
RECOGNIZE THIS SYMBOL
AS AN INDICATION OF
IMPORTANT SAFETY
INFORMATION
ST-A1226-01-00
FEATURING INDUSTRY STANDARD
R-410A REFRIGERANT
earth friendly refrigerant
e
ar
t
h
r
y r
dly
dl
e
n
i
fr
h
NOTE: Actual unit appearance
may vary.

Table of Contents

Questions and Answers

  • S
    stephanie33Sep 16, 2025
    What does it mean when my Rheem Air Conditioner has high head and low vapor pressures?
    • C
      Cody EspinozaSep 16, 2025
      If your Rheem Air Conditioner has high head pressure but low vapor pressures, there might be a restriction in the liquid line, expansion device, or filter drier. Remove or replace the defective component. Another cause could be a bad TXV, which would need to be replaced.
  • L
    Leroy GarciaSep 23, 2025
    What causes a gurgling noise in my Rheem Air Conditioner's liquid line?
    • S
      Spencer MasonSep 23, 2025
      If you hear a gurgling or pulsing noise at the expansion device or liquid line of your Rheem Air Conditioner, it's likely due to air or noncondensibles in the system. To resolve this, recover the refrigerant, evacuate the system, and then recharge it.
  • A
    Alexandria ByrdSep 7, 2025
    What causes gurgling noise in Rheem RA1436AJ1NA Air Conditioner?
    • A
      Angela HawkinsSep 7, 2025
      A gurgling or pulsing noise at the expansion device or liquid line in your Rheem Air Conditioner usually indicates air or noncondensibles in the system. To fix this, recover the refrigerant, evacuate the system, and recharge it.
  • P
    Patricia RushAug 27, 2025
    What to do if Rheem Air Conditioner compressor short cycles?
    • A
      Anthony JacksonAug 27, 2025
      If your Rheem Air Conditioner's compressor is short cycling, several factors could be responsible. First, check the voltage at the compressor terminals; it must be within ± 10% of the nameplate marking when the unit is operating. A defective overload protector could also be the cause, requiring replacement. Lastly, a refrigerant undercharge might be the issue, in which case you should add refrigerant.
  • S
    stephen97Aug 27, 2025
    What causes Rheem RA1436AJ1NA outdoor fan to run but compressor not?
    • D
      Daniel OneillAug 27, 2025
      If the outdoor fan of your Rheem Air Conditioner is running but the compressor isn't, it could be due to several reasons. A defective run or start capacitor may be the cause, requiring replacement. The contactor could also be defective and need replacement. Check for correct voltage at the compressor and ensure all connections are tight, as a loose connection could be the problem. The compressor might be stuck, grounded, have an open motor winding, or an open internal overload; wait at least 3 hours for the overload to reset, and if it remains open, replace the compressor. A low-voltage condition could also be the cause, in which case you should add start kit components.
  • J
    Janet WellsAug 28, 2025
    Why does my Rheem Air Conditioner have high head pressure in cooling mode?
    • W
      William KellyAug 29, 2025
      High head pressure in cooling mode for your Rheem Air Conditioner can result from a few issues. The outdoor coil might be dirty, so cleaning it is recommended. Refrigerant overcharge could also be the problem, requiring a correction of the system charge. If the outdoor fan isn't running, it needs repair or replacement. Finally, air or noncondensibles in the system could be the cause, requiring refrigerant recovery, evacuation, and recharge.
  • E
    Erin HinesAug 30, 2025
    Why is my Rheem RA1436AJ1NA Air Conditioner's indoor coil iced?
    • N
      nmcclainAug 30, 2025
      An iced indoor coil, accompanied by low vapor and a cool compressor in your Rheem Air Conditioner, can be attributed to several factors. Low indoor airflow could be the culprit; increase the blower speed or reduce restrictions, and replace the air filter. If you're operating below 65°F outdoors, consider adding a Low Ambient Kit. Moisture in the system can also lead to this issue, requiring refrigerant recovery, evacuation, recharge, and the addition of a filter drier. Lastly, a closed ID circuit might be the cause, necessitating repair or replacement of the ID coil.
  • K
    Katrina WilliamsSep 18, 2025
    Why does my Rheem Air Conditioner have low head and high vapor pressures?
    • P
      Patrick LeblancSep 18, 2025
      If your Rheem Air Conditioner is showing low head pressure but high vapor pressures, it could be caused by a bad TXV, which needs replacement. Alternatively, a bad compressor could be the issue, also requiring replacement.
  • R
    robinsoncynthiaSep 18, 2025
    What could cause high vapor pressure in my Rheem RA1436AJ1NA Air Conditioner?
    • J
      Jeffrey JonesSep 18, 2025
      If your Rheem Air Conditioner is showing high vapor pressure, it could be due to an excessive load, so recheck the load calculation. Alternatively, the compressor might be defective and need replacement.
  • N
    Nicholas RichardsonSep 8, 2025
    Why is my Rheem RA1436AJ1NA Air Conditioner not cooling properly?
    • S
      Sarah GriffinSep 8, 2025
      If your Rheem Air Conditioner isn't cooling enough, several factors could be responsible. The unit might be improperly sized, so recalculate the load. There could be improper indoor airflow; it should be about 400 CFM per ton. The refrigerant charge might be incorrect, so charge it according to the procedure on the unit's service panel. Air, noncondensibles, or moisture in the system can also cause this, in which case you should recover the refrigerant, evacuate, and recharge, adding a filter drier. Finally, a bad ID TXV could be the culprit, requiring replacement.

Summary

Important Safety Information

Installation

Location Selection and Mounting

Covers choosing optimal location, space limitations, customer satisfaction, and unit mounting guidelines.

Interconnecting Tubing and Line Sets

Details on tubing selection, sizing, installation, and adjustments for optimal system performance.

Wiring

Start-Up

Evacuation and Leak Testing

Detailed steps for system evacuation to remove moisture and air, followed by leak detection procedures.

Checking Refrigerant Charge

Methods for verifying and adjusting refrigerant charge using pressure, subcooling, and weight measurements.

Diagnostics

General Troubleshooting Chart

A table listing common symptoms, possible causes, and remedies for various unit issues.

Rheem RA1436AJ1NA Specifications

General IconGeneral
SEER Rating14
HSPF RatingNot Applicable
Voltage208/230 V
Phase1
Frequency60 Hz
RefrigerantR-410A
Compressor TypeScroll
Energy Efficiency Ratio (EER)11.5
Power SupplyElectric
TypeSplit System
Cooling Capacity36000 BTU/h