AIR COOLED
CONDENSING UNITS
92-104921-09-07 (5/16)
Printed in USA
[ ] indicates metric conversions.
Do not destroy this manual.
Please read carefully
and keep in a safe place
for future reference by a
serviceman.
WARNING
THESE INSTRUCTIONS
ARE INTENDED AS AN AID
TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR
PROPER INSTALLATION,
ADJUSTMENT, AND
OPERATION OF THIS
UNIT. READ THESE
INSTRUCTIONS
THOROUGHLY
BEFORE ATTEMPTING
INSTALLATION OR
OPERATION. FAILURE
TO FOLLOW THESE
INSTRUCTIONS MAY
RESULT IN IMPROPER
INSTALLATION,
ADJUSTMENT, SERVICE,
OR MAINTENANCE
POSSIBLY RESULTING IN
FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE,
PERSONAL INJURY, OR
DEATH.
INSTALLATION INSTRUCTIONS
(-)A13, (-)A14 & (-)A16 MODEL SERIES –
13, 14 & 16 SEER
WARNING:
RECOGNIZE THIS SYMBOL
AS AN INDICATION OF
IMPORTANT SAFETY
INFORMATION
ST-A1226-01-00
FEATURING INDUSTRY STANDARD
R-410A REFRIGERANT
earth friendly refrigerant
e
ar
t
h
r
y r
dly
dl
e
n
i
fr
h
NOTE: Actual unit appearance
may vary.

Table of Contents

Questions and Answers

  • L
    Leroy GarciaSep 23, 2025
    What causes a gurgling noise in my Rheem Air Conditioner's liquid line?
    • S
      Spencer MasonSep 23, 2025
      If you hear a gurgling or pulsing noise at the expansion device or liquid line of your Rheem Air Conditioner, it's likely due to air or noncondensibles in the system. To resolve this, recover the refrigerant, evacuate the system, and then recharge it.
  • M
    Michelle WilliamsAug 23, 2025
    Why are the registers sweating in my Rheem RA1436AJ1NA Air Conditioner system?
    • A
      Adam McdowellAug 23, 2025
      If the registers in your Rheem Air Conditioner system are sweating, it's likely due to low indoor airflow. Try increasing the blower speed or reducing any restrictions in the airflow. Replacing the air filter can also help.
  • S
    Shelby MillerAug 25, 2025
    How to troubleshoot a Rheem Air Conditioner that will not run?
    • K
      Kimberly HamiltonAug 26, 2025
      If your Rheem Air Conditioner unit won't run, several factors could be the cause. It could be due to a power outage or loose electrical connection, so check the voltage at the line voltage connections. The thermostat might be out of calibration, so try resetting it. A blown fuse or tripped breaker can also prevent the unit from running, so replace the fuses or reset the breaker. Other potential issues include a defective transformer (check the wiring and replace if necessary), an open high-pressure control (reset it), an open low-pressure control, a defective control board (check diagnostic codes), or miswiring of communications (check communication wiring).
  • P
    Patricia RushAug 27, 2025
    What to do if Rheem Air Conditioner compressor short cycles?
    • A
      Anthony JacksonAug 27, 2025
      If your Rheem Air Conditioner's compressor is short cycling, several factors could be responsible. First, check the voltage at the compressor terminals; it must be within ± 10% of the nameplate marking when the unit is operating. A defective overload protector could also be the cause, requiring replacement. Lastly, a refrigerant undercharge might be the issue, in which case you should add refrigerant.
  • S
    stephen97Aug 27, 2025
    What causes Rheem RA1436AJ1NA outdoor fan to run but compressor not?
    • D
      Daniel OneillAug 27, 2025
      If the outdoor fan of your Rheem Air Conditioner is running but the compressor isn't, it could be due to several reasons. A defective run or start capacitor may be the cause, requiring replacement. The contactor could also be defective and need replacement. Check for correct voltage at the compressor and ensure all connections are tight, as a loose connection could be the problem. The compressor might be stuck, grounded, have an open motor winding, or an open internal overload; wait at least 3 hours for the overload to reset, and if it remains open, replace the compressor. A low-voltage condition could also be the cause, in which case you should add start kit components.
  • S
    stephanie33Sep 16, 2025
    What does it mean when my Rheem Air Conditioner has high head and low vapor pressures?
    • C
      Cody EspinozaSep 16, 2025
      If your Rheem Air Conditioner has high head pressure but low vapor pressures, there might be a restriction in the liquid line, expansion device, or filter drier. Remove or replace the defective component. Another cause could be a bad TXV, which would need to be replaced.
  • R
    Richard BryanSep 13, 2025
    Why is the indoor coil of my Rheem RA1436AJ1NA iced, with low vapor pressure?
    • G
      gibsonchadSep 13, 2025
      If you notice low vapor pressure, a cool compressor, and an iced indoor coil in your Rheem Air Conditioner, it could be due to low indoor airflow. Try increasing the blower speed or reducing restrictions, and replace the air filter. If you're operating the unit below 65°F outdoors, consider adding a Low Ambient Kit. Moisture in the system can also cause this issue, so recover the refrigerant, evacuate, recharge, and add a filter drier. Finally, a closed ID circuit could be the problem, requiring repair or replacement of the ID coil.
  • M
    Mark ArnoldSep 15, 2025
    What causes fluctuating head and vapor pressures in a Rheem RA1436AJ1NA Air Conditioner?
    • C
      connernatalieSep 15, 2025
      If your Rheem Air Conditioner is experiencing fluctuating head and vapor pressures, it could be due to TXV hunting. Check the TXV bulb clamp and air distribution on the coil; consider replacing the TXV. Another potential cause is air or noncondensibles in the system, which requires recovering the refrigerant, evacuating, and recharging.
  • A
    anthony44Sep 5, 2025
    Why do my Rheem Air Conditioner registers sweat?
    • P
      palmerlisaSep 5, 2025
      Sweating registers in your Rheem Air Conditioner system are typically caused by low indoor airflow. To resolve this, increase the speed of the blower or reduce any restrictions. Also, replace the air filter.
  • K
    Kelly RodriguezSep 3, 2025
    What does low head and high vapor pressures mean for Rheem Air Conditioner?
    • A
      Alejandro WadeSep 3, 2025
      Low head pressure coupled with high vapor pressures in your Rheem Air Conditioner can point to a bad TXV, which requires replacement. Another potential cause is a bad compressor, which would also need replacing.

Summary

Important Safety Information

Installation

Location Selection and Mounting

Covers choosing optimal location, space limitations, customer satisfaction, and unit mounting guidelines.

Interconnecting Tubing and Line Sets

Details on tubing selection, sizing, installation, and adjustments for optimal system performance.

Wiring

Start-Up

Evacuation and Leak Testing

Detailed steps for system evacuation to remove moisture and air, followed by leak detection procedures.

Checking Refrigerant Charge

Methods for verifying and adjusting refrigerant charge using pressure, subcooling, and weight measurements.

Diagnostics

General Troubleshooting Chart

A table listing common symptoms, possible causes, and remedies for various unit issues.

Rheem RA1436AJ1NA Specifications

General IconGeneral
SEER Rating14
HSPF RatingNot Applicable
Voltage208/230 V
Phase1
Frequency60 Hz
RefrigerantR-410A
Compressor TypeScroll
Energy Efficiency Ratio (EER)11.5
Power SupplyElectric
TypeSplit System
Cooling Capacity36000 BTU/h