Flashing lower case c
A command for first stage cooling has been received
Flashing upper case C
A command for second stage cooling has been received
The 3-minute time delay can be bypassed when a command for compressor
operation is present by pressing the TEST button for 1 second and releasing.
The compressor will begin operation and the dual 7-segment will stop flashing.
30 Second Minimum Run Timer
The ICC has a built in 30 second minimum unit run time. If a command for com-
pressor operation is received by the ICC and the command is removed, the com-
pressor will continue to operate for 30 seconds. The dual 7-segment LEDs will
flash “c” or “C” while the minimum run timer is active.
1 Second Compressor/Fan Delay
The ICC starts/stops the outdoor fan one (1) second after the start/stop of the
compressor upon a command for compressor operation to minimize current
inrush and/or voltage drop.
11.4 Active Compressor Protection Mode
The ICC actively protects the compressor from harmful operation during a fault
condition.
When the ICC detects a condition that could damage the compressor, the ICC will
enter active protection mode and lockout compressor operation
The condition causing active protection must be resolved then the ICC can be
reset to restart the system.
There are five (5) active protection modes:
1) Low Pressure Control Lockout
The ICC will display a flashing “L” followed by a flashing 21 when a low pressure
control lockout occurs.
The ICC addresses low pressure control faults differently depending on the mode
of unit operation (cooling or heating mode).
Active Protection Code L21 Open low pressure control
Cooling Mode
If the LPC opens three (3) times during the same command for cooling operation,
the ICC will lockout the compressor to keep it from continuing to operate and flash
a L” on the dual 7-segment LEDs followed by a “21”.
IMPORTANT: This mode of active protection must be manually reset.
2) High Pressure Control Lockout
If the HPC opens three (3) times during the same command for unit operation, the
ICC will lockout the compressor to keep it from continuing to operate and flash a
L” on the dual 7-segment LEDs followed by a “29”.
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
20