11.9 ICC Control Operation with Conventional Thermostat Wiring
Installation Verification
24V AC power on R&C must be present at the ICC for it to operate
Line voltage must be present at the ICC for the compressor and the outdoor fan
to operate
The ICC displays a “0” for standby mode. Standby mode indicates line voltage
and 24VAC are present at the ICC and there is not a call for unit operation from
the thermostat.
Zero (0) displayed
The unit is in standby
Call for Compressor Operation (Y1 LED)
If a call for compressor operation is received by the ICC (first stage/second stage
cooling or first stage/second stage heating), the red Y1 LED will illuminate.
The ICC has an on/off fan delay of one (1) second for each stage of heating or
cooling.
The ICC ignores the lower pressure control for the first 90 seconds of compressor
operation.
On heat pumps, the ICC ignores the LPC during the defrost cycle.
The dual 7-segment LED displays five (5) operational status codes.
1) First Stage Cooling Operation When the ICC receives a call for first stage
cooling operation, a lower case “c” is displayed on the dual 7-segment LEDs.
Lower case “c” indicates first stage cooling operation
2) Second Stage Cooling Operation When the ICC receives a call for second
stage cooling operation, an upper case “C” is displayed on the dual 7-segment
LEDs.
Upper case “C” indicates second stage cooling operation
3-minute Anti-short Cycle Timer
The ICC has a built in 3-minute time delay between compressor operations to
protect the compressor against short cycling. The dual 7-segment LEDs will flash
“c” or “C” while the short cycle timer is active and a call for unit operation is
received.
Flashing lower case c
A call for first stage cooling has been received
Flashing upper case C
A call for second stage cooling has be received
The 3-minute time delay can be bypassed when a call for compressor operation is
present by pressing the TEST button for 1 second and releasing. The compres-
sor will begin operation and the dual 7-segment will stop flashing.
29
CONVENTIONAL THERMOSTAT WIRING