Rheem RH1P3617STANJA - (-)H1 P With Electric Heat - continued

Rheem RH1P3617STANJA
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
? Heater Kit Connection Type  A=Breaker  B=Terminal Block  C=Pullout Disconnect
¿ D Voltage = 480 Volts.
*Values only. No single point kit available.
NOTES:
Electric heater BTUH - (heater watts + motor watts) x 3.412 (see airflow table for motor watts.)
Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
Motor load is included in single circuit or circuit 1 of multiple circuits.
Heater loads are balanced on 3 phase models with 3 or 6 heating elements only.
Electric heater kits are not permitted for use with 115 volt air-handlers (A voltage).
J Voltage (208/240V) single phase air-handlers are designed to be used with single or three phase 208/240V electric heaters. To connect 3
phase power to the air handler terminal block, bring only two leads to terminal block, cap, insulate, and fully secure the third lead.
Do not install 480V electric heaters in 208/240V air-handlers.
Do not install 208/240V electric heaters in 480V air-handlers.
If the heater kit is listed under both single and multiple circuits, the heater kit is shipped from factory as multiple circuits. For single phase appli-
cations, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. See Section 6.2 for details.
RXBH-1724A07C 5.4/7.2 3/60 3-2.4 SINGLE 15.0/17.3 5.2 26/29 30/30
RXBH-1724A10C 7.2/9.6 3/60 3-3.2 SINGLE 20.0/23.1 5.2 32/36 35/40
RXBH-1724A15C 10.8/14.4 3/60 3-4.8 SINGLE 30.0/34.6 5.2 44/50 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-5.68 SINGLE 35.6/41.0 5.2 51/58 60/60
RXBH-24A20C* 14.4/19.2 3/60 6-3.2 SINGLE 40.0/46.2 5.2 57/65 60/70
7.2/9.6 3/60 3-3.2 MULTIPLE CKT 1 20.0/23.1 5.2 32/36 35/40
RXBH-24A20C
7.2/9.6 3/60 3-3.2 MULTIPLE CKT 2 20.0/23.1 0 25/29 25/30
RXBH-24A25C* 18.0/24.0 3/60 6-4.0 SINGLE 50.0/57.8 5.2 69/79 70/80
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1 25.0/28.9 5.2 38/43 40/45
6024S
RXBH-24A25C
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2 25.0/28.9 0 32/37 35/40
RXBH-24A30C* 21.6/28.8 3/60 6-4.8 SINGLE 60.0/69.4 5.2 82/94 90/100
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 1 30.0/34.7 5.2 44/50 45/50
RXBH-24A30C
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 2 30.0/34.7 0 38/44 40/45
RXBH-24A07D 7.2 3/60 3-2.4 SINGLE 8.7 2.2 14 15
RXBH-24A10D 9.6 3/60 3-3.2 SINGLE 11.6 2.2 18 20
RXBH-24A15D 14.4 3/60 3-4.8 SINGLE 17.3 2.2 25 25
RXBH-24A18D 17 3/60 6-2.84 SINGLE 20.4 2.2 29 30
RXBH-24A20D 19.2 3/60 6-3.2 SINGLE 23.2 2.2 32 35
RXBH-24A25D 24.0 3/60 6-4.0 SINGLE 28.8 2.2 39 40
RXBH-24A30D* 28.8 3/60 6-4.8 SINGLE 34.6 2.2 46 50
3.13.6.1 ELECTRICAL DATA – WITH ELECTRIC HEAT: (-)H1P - continued
AIR HANDLER
MODEL
(-)H1P
HEATER
MODEL
NO.
HEATER
KW
(208/240V¿)
(480V)
PH/HZ
NO.
ELEMENTS
- KW PER
TYPE SUPPLY
CIRCUIT
SINGLE CIRCUIT
MULTIPLE CIRCUIT
HEATER
AMPS
MOTOR
AMPS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
OVERCURRENT
PROTECTION