Loading...
Air
Gross Systems Performance Data
RKNL-B Series
26
GROSS SYSTEMS PERFORMANCE DATA—B102
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 4100 [6035] 3200 [1510] 2700 [1274] 4100 [6035] 3200 [1510] 2700 [1274] 4100 [6035] 3200 [1510] 2700 [1274]
DR
0 .05 .08 0 .05 .08 0 .05 .08
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
113.8 [33.4]
69.9 [20.5]
6.4
108.3 [31.7]
56.3 [16.5]
6.3
105.2 [30.8]
49.3 [14.5]
6.2
110.1 [32.3]
91.3 [26.8]
6.3
104.7 [30.7]
75.3 [22.1]
6.2
101.7 [29.8]
67.0 [19.6]
6.1
105.0 [30.8]
103.1 [30.2]
6.2
99.9 [29.3]
86.0 [25.2]
6.1
97.0 [28.4]
77.0 [22.6]
6.0
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
113.7 [33.3]
71.7 [21.0]
6.7
108.2 [31.7]
57.9 [17.0]
6.6
105.1 [30.8]
50.8 [14.9]
6.5
110.0 [32.2]
93.1 [27.3]
6.7
104.6 [30.7]
76.9 [22.5]
6.5
101.7 [29.8]
68.6 [20.1]
6.4
104.9 [30.7]
104.9 [30.8]
6.6
99.8 [29.2]
87.6 [25.7]
6.4
96.9 [28.4]
78.5 [23.0]
6.3
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
112.9 [33.1]
72.6 [21.3]
7.1
107.5 [31.5]
58.8 [17.2]
6.9
104.4 [30.6]
51.6 [15.1]
6.8
109.2 [32.0]
94.0 [27.6]
7.0
103.9 [30.5]
77.8 [22.8]
6.8
101.0 [29.6]
69.4 [20.3]
6.7
104.1 [30.5]
104.1 [30.5]
6.9
99.1 [29.0]
88.5 [25.9]
6.7
96.2 [28.2]
79.4 [23.3]
6.7
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
111.5 [32.7]
72.9 [21.4]
7.4
106.1 [31.1]
59.0 [17.3]
7.3
103.1 [30.2]
51.9 [15.2]
7.2
107.8 [31.6]
94.2 [27.6]
7.4
102.5 [30.0]
78.0 [22.9]
7.2
99.6 [29.2]
69.6 [20.4]
7.1
102.7 [30.1]
102.7 [30.1]
7.3
97.7 [28.6]
88.7 [26.0]
7.1
94.9 [27.8]
79.6 [23.3]
7.0
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
109.4 [32.1]
72.2 [21.2]
7.8
104.1 [30.5]
58.5 [17.2]
7.6
101.1 [29.6]
51.5 [15.1]
7.5
105.7 [31.0]
93.6 [27.4]
7.7
100.5 [29.5]
77.5 [22.7]
7.6
97.7 [28.6]
69.3 [20.3]
7.4
100.6 [29.5]
100.6 [29.5]
7.7
95.7 [28.0]
88.2 [25.9]
7.5
93.0 [27.3]
79.3 [23.3]
7.4
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
106.6 [31.2]
70.7 [20.7]
8.2
101.4 [29.7]
57.3 [16.8]
8.0
98.6 [28.9]
50.5 [14.8]
7.9
102.9 [30.2]
92.1 [27.0]
8.1
97.9 [28.7]
76.4 [22.4]
8.0
95.1 [27.9]
68.2 [20.0]
7.8
97.8 [28.7]
97.8 [28.7]
8.1
93.0 [27.3]
87.0 [25.5]
7.9
90.4 [26.5]
78.2 [22.9]
7.8
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
103.2 [30.2]
68.4 [20.1]
8.7
98.1 [28.8]
55.4 [16.2]
8.4
95.4 [28.0]
48.9 [14.3]
8.3
99.4 [29.1]
89.7 [26.3]
8.6
94.6 [27.7]
74.5 [21.8]
8.4
91.9 [26.9]
66.6 [19.5]
8.2
94.3 [27.6]
94.3 [27.6]
8.5
89.8 [26.3]
85.2 [25.0]
8.3
87.2 [25.6]
76.6 [22.5]
8.2
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
99.0 [29.0]
65.2 [19.1]
9.1
94.2 [27.6]
52.8 [15.5]
8.9
91.5 [26.8]
46.4 [13.6]
8.8
95.3 [27.9]
86.7 [25.4]
9.0
90.7 [26.6]
72.0 [21.1]
8.8
88.1 [25.8]
64.3 [18.9]
8.7
90.2 [26.4]
90.2 [26.4]
8.9
85.8 [25.1]
82.5 [24.2]
8.7
83.4 [24.4]
74.3 [21.8]
8.6
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
94.2 [27.6]
61.3 [18.0]
9.6
89.6 [26.3]
49.6 [14.5]
9.3
87.1 [25.5]
43.7 [12.8]
9.2
90.5 [26.5]
82.7 [24.2]
9.5
86.1 [25.2]
68.7 [20.1]
9.3
83.7 [24.5]
61.5 [18.0]
9.1
85.4 [25.0]
85.4 [25.0]
9.4
81.3 [23.8]
79.4 [23.3]
9.2
78.9 [23.1]
71.4 [20.9]
9.1
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions
GROSS SYSTEMS PERFORMANCE DATA—B120
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 4800 [2265] 3750 [1770] 3200 [1510] 4800 [2265] 3750 [1770] 3200 [1510] 4800 [2265] 3750 [1770] 3200 [1510]
DR
0 .03 .07 0 .03 .07 0 .03 .07
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
149.3 [43.8]
99.7 [29.2]
7.3
142.1 [41.6]
81.0 [23.7]
7.2
138.3 [40.5]
71.9 [21.1]
7.1
139.6 [40.9]
117.9 [34.6]
7.2
132.8 [38.9]
97.5 [28.6]
7.0
129.3 [37.9]
87.6 [25.7]
6.9
130.9 [38.4]
130.9 [38.4]
7.1
124.6 [36.5]
109.7 [32.2]
6.9
121.3 [35.5]
99.1 [29.1]
6.8
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
147.2 [43.1]
99.2 [29.1]
7.8
140.0 [41.0]
80.5 [23.6]
7.6
136.3 [39.9]
71.5 [21.0]
7.5
137.4 [40.3]
117.1 [34.3]
7.7
130.8 [38.3]
97.0 [28.4]
7.5
127.3 [37.3]
87.1 [25.5]
7.4
128.8 [37.7]
128.8 [37.8]
7.6
122.6 [35.9]
109.3 [32.0]
7.4
119.3 [35.0]
98.7 [28.9]
7.3
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
144.7 [42.4]
98.0 [28.7]
8.3
137.7 [40.4]
79.7 [23.4]
8.1
134.0 [39.3]
70.8 [20.8]
8.0
135.0 [39.6]
116.2 [34.1]
8.2
128.5 [37.7]
96.3 [28.2]
8.0
125.0 [36.6]
86.4 [25.3]
7.9
126.4 [37.0]
126.4 [37.1]
8.0
120.2 [35.2]
108.4 [31.8]
7.8
117.0 [34.3]
98.0 [28.7]
7.7
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
142.0 [41.6]
96.8 [28.4]
8.8
135.1 [39.6]
78.7 [23.1]
8.6
131.5 [38.5]
70.0 [20.5]
8.5
132.3 [38.8]
114.9 [33.7]
8.7
125.9 [36.9]
95.2 [27.9]
8.5
122.5 [35.9]
85.5 [25.1]
8.4
123.6 [36.2]
123.6 [36.2]
8.6
117.7 [34.5]
107.5 [31.5]
8.4
114.5 [33.6]
97.2 [28.5]
8.3
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
139.0 [40.7]
95.1 [27.9]
9.4
132.3 [38.8]
77.4 [22.7]
9.1
128.8 [37.7]
68.8 [20.2]
9.0
129.3 [37.9]
113.2 [33.2]
9.2
123.0 [36.0]
93.8 [27.5]
9.0
119.7 [35.1]
84.3 [24.7]
8.9
120.7 [35.4]
120.7 [35.4]
9.1
114.8 [33.6]
106.1 [31.1]
8.9
111.8 [32.8]
96.0 [28.1]
8.8
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
135.8 [39.8]
93.1 [27.3]
9.9
129.2 [37.9]
75.7 [22.2]
9.7
125.7 [36.8]
67.3 [19.7]
9.6
126.0 [36.9]
111.1 [32.6]
9.8
119.9 [35.1]
92.2 [27.0]
9.6
116.7 [34.2]
82.9 [24.3]
9.5
117.4 [34.4]
117.4 [34.4]
9.7
111.7 [32.7]
104.4 [30.6]
9.5
108.7 [31.9]
94.5 [27.7]
9.3
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
132.2 [38.7]
90.7 [26.6]
10.6
125.8 [36.9]
73.8 [21.6]
10.3
122.5 [35.9]
65.7 [19.3]
10.2
122.5 [35.9]
108.8 [31.9]
10.4
116.5 [34.1]
90.2 [26.4]
10.2
113.4 [33.2]
81.1 [23.8]
10.1
113.8 [33.4]
113.8 [33.4]
10.3
108.3 [31.7]
102.5 [30.0]
10.1
105.4 [30.9]
92.8 [27.2]
9.9
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
128.4 [37.6]
88.0 [25.8]
11.2
122.2 [35.8]
71.6 [21.0]
10.9
118.9 [34.8]
63.6 [18.6]
10.8
118.7 [34.8]
106.2 [31.1]
11.1
112.9 [33.1]
88.1 [25.8]
10.8
109.9 [32.2]
79.3 [23.3]
10.7
110.0 [32.2]
110.0 [32.2]
11.0
104.7 [30.7]
100.3 [29.4]
10.7
101.9 [29.9]
90.8 [26.6]
10.6
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
124.3 [36.4]
85.0 [24.9]
11.9
118.3 [34.7]
69.2 [20.3]
11.6
115.1 [33.7]
61.5 [18.0]
11.4
114.6 [33.6]
103.1 [30.2]
11.7
109.0 [31.9]
85.6 [25.1]
11.5
106.1 [31.1]
77.0 [22.6]
11.3
105.9 [31.0]
105.9 [31.0]
11.6
100.8 [29.5]
97.9 [28.7]
11.3
98.1 [28.8]
88.7 [26.0]
11.2

Related product manuals