Air
Electrical Data
RKNL-B Series
36
ELECTRICAL DATA – RKNL SERIES
Amps (LRA, each) 20 33
Volts
Minimum Overcurrent Protection Device Size
575
30
Maximum Overcurrent Protection Device Size
35
Compressor Motor
No.
2
Volts
575
Phase
3
RPM
3450
HP, Compressor 1
5 3/4
Amps (LRA), Comp. 1
54
Amps (RLA), Comp. 2
Unit Information
Unit Operating Voltage Range
7.4
518-632
Condenser Motor
No.
2
Volts
575
Phase
1
HP
1/2
Amps (FLA, each)
0.5
Amps (LRA, each)
2.2
Evaporator Fan
No.
1
Volts
575
Phase
3
HP
3
Amps (FLA, each)
8 8
5
3
575
1
2.2
0.5
1/2
1
575
2
7.4
54
5 3/4
3450
3
575
2
35
30
575
518-632
Minimum Circuit Ampacity
28 28
HP, Compressor 2
5 1/4 5 1/4
Amps (LRA), Comp. 2
50 50
Amps (RLA), Comp. 1
7.7 7.7
B151YL B151YM