F. HEATING AIRFLOW ADJUSTMENTS
Heating airflow may be adjusted +10% or –10% from nominal airflow using switches 5 & 6.
Refer to Figure 33 for switch positions to achieve the desired adjustments in airflow.
NOTE: Continuous fan speed is NOT affected by switches 5 & 6.
G. COOLING DELAY PROFILES
The unit is shipped with a default ON/OFF delay profile for maximum efficiency. This default
may be overridden to maximize comfort by using one of the alternate profiles. ON delay pro-
files are shown in Figure 31.
OFF delay profiles are shown in Figure 32.
IMPORTANT: Blower ON delay profiles are not used in heating mode.
FIGURE 33
HEATING AIRFLOW ADJUSTMENTS
HEATING
SELECTION SWITCH 5 SWITCH 6 AIRFLOW
POSITION POSITION ADJUSTMENT
A OFF OFF NONE
B ON OFF 10%
C OFF ON -10%
D ON ON NONE
O
N
O
N
O
N
O
N
A
5
6
5
6
5
6
5
6
BCD