1 Horsepower per Compressor
2. Amp Draw Per Motor. Multiply Value by Number of Motors to Determine Total Amps.
-B048CK08 -B048CK10 -B048DK10 -B048JK06 -B048JK08 -B048JK10
Unit Operating Voltage
Range
1
87-253 187-253 414-506 187-253 187-253 187-253
M
inimum Circuit
A
mmpacity
2
4/24 24/24 12 34/34 34/34 34/34
M
inimum Overcurrent
Protection Device Size
25/25 25/25 15 35/35 35/35 35/35
Maximum Overcurrent
P
rotection Device Size
35/35 35/35 20 50/50 50/50 50/50
N
o. 111111
V
olts 208/230 208/230 460 208/230 208/230 208/230
Phase 3 3 3 1 1 1
HP 444444
R
PM 3450 3450 3450 3450 3450 3450
Amps (RLA) 13.7/13.7 13.7/13.7 6.2 21.8/21.8 21.8/21.8 21.8/21.8
Amps (LRA) 83.1/83.1 83.1/83.1 41 117/117 117/117 117/117
No. 111111
Volts 208/230 208/230 460 208/230 208/230 208/230
Phase 1 1 1 1 1 1
HP 1/3 1/3 1/3 1/3 1/3 1/3
Amps (FLA) 2 2 1 2 2 2
Amps (LRA) 3.9 3.9 2.2 3.9 3.9 3.9
No. 111111
Volts 208/230 208/230 460 208/230 208/230 208/230
Phase 1 1 1 1 1 1
HP 3/4 3/4 3/4 3/4 3/4 3/4
Amps (FLA) 4.4 4.4 2.3 4.4 4.4 4.4
Amps (LRA) 9.5 9.5 5 9.5 9.5 9.5
Condenser MotorEvaporator Fan
ELECTRICAL DATA - RRNL SERIES
Unit InformationCompressor Motor
-
C060CK10 -C060JK10
1
97-253 197-253
32/32 43/43
35/35 45/45
4
5/45 60/60
11
208/230 208/230
31
5
5
3450 3450
1
7.9/17.9 26.4/26.4
110/110 134/134
11
208/230 208/230
11
1/3 1/3
22
3.9 3.9
11
208/230 208/230
11
11
7.6 7.6
00