EasyManua.ls Logo

Rheem RRRL - Page 74

Rheem RRRL
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74
1 Horsepower per Compressor
2. Amp Draw Per Motor. Multiply Value by Number of Motors to Determine Total Amps.
-
B048CK08 -B048CK10 -B048JK08 -B048JK10
Unit Operating Voltage
Range
197-253 197-253 197-253 187-253
Minimum Circuit
Ammpacity
22/22 22/22 31/31 31/31
Minimum Overcurrent
P
rotection Device Size
25/25 25/25 40/40 40/40
Maximum Overcurrent
Protection Device Size
30/30 30/30 50/50 50/50
No. 1 1 1 1
Volts 208/230 208/230 208/230 208/230
Phase 3 3 1 1
HP 5 1/4 5 1/4 5 1/4 5 1/4
RPM 3450 3450 3450 3450
Amps (RLA) 13.5/13.5 13.5/13.5 21.2/21.2 21.2/21.2
Amps (LRA) 88/88 88/88 96/96 96/96
No. 1 1 1 1
Volts 208/230 208/230 208/230 208/230
Phase 1 1 1 1
HP 1/3 1/3 1/3 1/3
Amps (FLA) 1.5 1.5 1.5 1.5
Amps (LRA) 3 3 3 3
No. 1 1 1 1
Volts 208/230 208/230 208/230 208/230
Phase 1 1 1 1
HP 3/4 3/4 3/4 3/4
Amps (FLA) 3 3 3 3
Amps (LRA) 0 0 0 0
Condenser MotorEvaporator Fan
ELECTRICAL DATA - RRRL SERIES
Unit InformationCompressor Motor
-B060CK10 -B060JK10
197-253 197-253
28/28 38/38
35/35 45/45
45/45 60/60
11
208/230 208/230
31
7 6 2/3
3
450 3450
17.6/17.6 25.6/25.6
123/123 118/118
11
208/230 208/230
11
1/3 1/3
22
3.9 3.9
11
208/230 208/230
11
11
44
00

Table of Contents

Related product manuals