73
1 Horsepower per Compressor
2. Amp Draw Per Motor. Multiply Value by Number of Motors to Determine Total Amps.
-
B036CK06 -B036CK08 -B036CK10 -B036JK06 -B036JK08 -B036JK10
Unit Operating Voltage
Range
197-253 197-253 197-253 197-253 197-253 197-253
Minimum Circuit
Ammpacity
17/17 17/17 17/17 24/24 24/24 24/24
Minimum Overcurrent
P
rotection Device Size
20/20 20/20 20/20 30/30 30/30 30/30
Maximum Overcurrent
Protection Device Size
25/25 25/25 25/25 40/40 40/40 40/40
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 208/230 208/230 208/230
Phase 3 3 3 1 1 1
HP 4 4 4 4 4 4
RPM 3450 3450 3450 3450 3450 3450
Amps (RLA) 11.2/11.2 11.2/11.2 11.2/11.2 16.7/16.7 16.7/16.7 16.7/16.7
Amps (LRA) 58/58 58/58 58/58 82/82 82/82 82/82
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1 1 1 1 1 1
HP 1/6 1/6 1/6 1/6 1/6 1/6
Amps (FLA) 0.6 0.6 0.6 0.6 0.6 0.6
Amps (LRA) 1.5 1.5 1.5 1.5 1.5 1.5
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1 1 1 1 1 1
HP 1/2 1/2 1/2 1/2 1/2 1/2
Amps (FLA) 2 2 2 2 2 2
Amps (LRA) 0 0 0 0 0 0
Unit InformationCompressor MotorCondenser MotorEvaporator Fan
ELECTRICAL DATA - RRRL SERIES
-B024JK06
197-253
15/15
20/20
20/20
1
208/230
1
2 5/6
3450
10.3/10.3
52/52
1
208/230
1
1/6
0.6
1.5
1
208/230
1
1/3
1
0

Table of Contents