1 Horsepower per Compressor
2. Amp Draw Per Motor. Multiply Value by Number of Motors to Determine Total Amps.
-B048CK06 -B048CK08 -B048CK10 -B048JK06 -B048JK08 -B048JK10
Unit Operating Voltage
Range
1
87-253 187-253 187-253 187-253 187-253 187-253
Minimum Circuit
Ammpacity
26/26 26/26 26/26 36/36 36/36 36/36
Minimum Overcurrent
Protection Device Size
30/30 30/30 30/30 40/40 40/40 40/40
Maximum Overcurrent
Protection Device Size
35/35 35/35 35/35 50/50 50/50 50/50
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 208/230 208/230 208/230
Phase 3 3 3 1 1 1
H
P 444444
R
PM 3450 3450 3450 3450 3450 3450
Amps (RLA) 13.7/13.7 13.7/13.7 13.7/13.7 21.8/21.8 21.8/21.8 21.8/21.8
Amps (LRA) 83.1/83.1 83.1/83.1 83.1/83.1 117/117 117/117 117/117
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1 1 1 1 1 1
HP 1/3 1/3 1/3 1/3 1/3 1/3
Amps (FLA) 2 2 2 2 2 2
Amps (LRA) 3.9 3.9 3.9 3.9 3.9 3.9
No. 111111
Volts 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1 1 1 1 1 1
HP 3/4 3/4 3/4 3/4 3/4 3/4
Amps (FLA) 6 6 6 6 6 6
Amps (LRA) 0 0 0 0 0 0
ELECTRICAL DATA - RRPL SERIES
Unit InformationCompressor MotorCondenser MotorEvaporator Fan
-B060CK10 -B060JK10
197-253 197-253
32/32 42/42
35/35 45/45
4
5/45 60/60
11
208/230 208/230
31
55
3450 3450
17.6/17.6 25.6/25.6
123/123 118/118
11
208/230 208/230
11
1/3 1/3
22
3.9 3.9
11
208/230 208/230
11
11
7.6 7.6
00