1 Horsepower per Compressor
2. Amp Draw Per Motor. Multiply Value by Number of Motors to Determine Total Amps.
-B042CK04 -B042CK06 -B042CK08 -B042CK10 -B042JK04 -B042JK06 -B042JK08 -B042JK10
Unit Operating Voltage
Range
187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253
M
inimum Circuit
Ammpacity
24/24 24/24 24/24 24/24 29/29 29/29 29/29 29/29
M
inimum Overcurrent
Protection Device Size
25/25 25/25 25/25 25/25 30/30 30/30 30/30 30/30
M
aximum Overcurrent
Protection Device Size
35/35 35/35 35/35 35/35 45/45 45/45 45/45 45/45
N
o. 11111111
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 3 3 3 3 1 1 1 1
HP 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2
RPM 3450 3450 3450 3450 3450 3450 3450 3450
Amps (RLA) 13.5/13.5 13.5/13.5 13.5/13.5 13.5/13.5 17.9/17.9 17.9/17.9 17.9/17.9 17.9/17.9
Amps (LRA) 88/88 88/88 88/88 88/88 112/112 112/112 112/112 112/112
No. 11111111
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1 1 1 1 1 1 1 1
HP 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3
Amps (FLA) 2 2 2 2 2 2 2 2
Amps (LRA) 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
No. 1 1 1 1 1 1 1 1
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1 1 1 1 1 1 1 1
HP 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Amps (FLA) 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
Amps (LRA) 0 0 0 0 0 0 0 0