1 Horsepower per Compressor
2. Amp Draw Per Motor. Multiply Value by Number of Motors to Determine Total Amps.
-B036CK04 -B036CK06 -B036CK08 -B036CK10 -B036JK04 -B036JK06 -B036JK08 -B036JK10
U
nit Operating Voltage
R
ange
1
87-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253
Minimum Circuit
Ammpacity
19/19 19/19 19/19 19/19 27/27 27/27 27/27 27/27
Minimum Overcurrent
Protection Device Size
20/20 20/20 20/20 20/20 30/30 30/30 30/30 30/30
Maximum Overcurrent
Protection Device Size
25/25 25/25 25/25 25/25 40/40 40/40 40/40 40/40
No. 11111111
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 3 3 3 3 1 1 1 1
H
P 3 1/3 3 1/3 3 1/3 3 1/3 3 1/3 3 1/3 3 1/3 3 1/3
R
PM 3450 3450 3450 3450 3450 3450 3450 3450
A
mps (RLA) 10.4/10.4 10.4/10.4 10.4/10.4 10.4/10.4 16.7/16.7 16.7/16.7 16.7/16.7 16.7/16.7
Amps (LRA) 88/88 88/88 88/88 88/88 79/79 79/79 79/79 79/79
No. 1 1 1 1 1 1 1 1
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1 1 1 1 1 1 1 1
HP 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3
Amps (FLA) 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
Amps (LRA) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
No. 11111111
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1 1 1 1 1 1 1 1
HP 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Amps (FLA) 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
Amps (LRA) 0 0 0 0 0 0 0 0
ELECTRICAL DATA - RRPL SERIES
Unit InformationCompressor MotorCondenser MotorEvaporator Fan