EasyManua.ls Logo

Rickard MCU 2 - Page 25

Rickard MCU 2
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
RICKARD 2019
MLM INTEGRATION WITH BMS
The airflow data can also be monitored under the Data/Flow tab on the Diffuser controller.
 Valid – indicates the MCU had all the necessary information to do a valid airflow calculation.
 Distribute if a single airflow sensor is installed per control zone, the ‘distribute’ function should be acti-
vated in Flow setup. The measured pressure is then distributed to all the other diffusers in that zone for a
total zone airflow calculation. Should each diffuser in the zone have airflow sensors fitted, this function
should not be selected. Note if more than one, but not all diffusers in a zone are fitted with airflow sen-
sors, the distribute function for the zone will only work off one pressure sensor.
 No constants found – update the MCU Flow coefficients or check the diffuser type.
Once this check list is confirmed, the user must select Pressure present under the ‘Flow setup’ tab on the Diffus-
er controller node.
If the air handling unit is in operation, the flow and pressure values will now be displayed on the Diffuser con-
troller icon on a horizontal bar just below the heater demand output.