F10 - 5
METHOD 2 - SEMI-FLANGE COLLAR
A) Follow item C from METHOD 1.
B) Align the air tube and attached adjustable collar so air tube is centered in the
burner access hole of the boiler/furnace unit. Mark the center of the two holes in the
ADJUSTABLE COLLAR on to the front plate of the heating unit. Then drill 1/4 inch
(6.5 mm) holes through the front plate of the unit, using marks as a guide.
C) Install two short BOLTS (1) through the front plate of the heating unit from the
inside, and secure on the outside using the two special CHROME NUTS (2).
D) Follow item D from METHOD 1.
METHOD 3 - PEDESTAL MOUNT
Secure the MOUNTING FLANGE to MOUNTING PEDESTAL using the hardware
provided with the pedestal. Secure burner to MOUNTING FLANGE as in METHOD 1,
items A, C and D.
NOTE: It is suggested that the pedestal be anchored in position on the floor by
installing brackets over the pedestal tube and securing brackets to the floor.
ELECTRICAL CONNECTIONS
It is advisable to leave the control box off the sub-base while completing the electrical
connections to the burner.
WARNING: WHEN THE COMBUSTION CHAMBER IS LINED WITH A REFRAC-
TORY MATERIAL, IT IS IMPERATIVE THAT THE END CONE NOT PROTRUDE INTO
THE CHAMBER AREA, AS EXCESSIVE HEAT AT BURNER SHUT-DOWN WILL
DAMAGE THE END CONE.
1) Wire access hole
(Use BX electrical connector)
2) Earth ground conductor terminal
(GREEN WIRE)
3) Hot conductor terminal
(BLACK WIRE)
4) Neutral conductor terminal
(WHITE WIRE)
5) Strain relief clamp
WARNING: The hot (black) wire
must be connected to the
L ter-
minal and the neutral (white)
wire must be connected to the
N
terminal or the primary safety
control will be damaged.
Do not connect either wire to the
Terminal.
S7454