73
RECYCLING AND DISPOSAL
73
APPENDIX
APPENDIX
Menu
Par.
No.
Nr. dis-
played
Display
Description Range
Default
setting
UM
Access
type
Category
M1 48
DHW
tank
set-
point
Establishes the DHW indirect storage tank set-point
Par. 35 in mode 2.
104-160
(40-71)
122 (50) °F (°C) U DHW
M1 92
Fan
Speed
Maxi-
mum
Denes the fan rpm at max. power (it depends on
the model and is dened at Par. 98).
0-12750
Dened
by Par. 98
RPM I General
M1 93
Fan
Speed
Mini-
mum
Denes the fan rpm at minimum power (it depends
on the model and is dened at Par. 98).
0-12750
Dened
by Par. 98
RPM I General
M1 94
Fan
Speed
Ignition
Denes the fan rpm when the boiler is switched on
(it depends on the model and is dened at Par. 98).
0-12750
Dened
by Par. 98
RPM I General
M1 116
Prog.
Input 1.
The value of this parameter is dened by Par. 97.
0 Disabled
1 Water pressure
sensor
2 CH ow switch
3 Flue pressure
switch
Dened
by Par. 97
I General
M1 117
Prog
Input 2.
The value of this parameter is dened by Par. 97.
0 Disabled
1 DHW ow
sensor
2 DHW ow
switch
3 CH ow sensor
Dened
by Par. 97
I General
M1 118
Prog
Input 3.
The value of this parameter is dened by Par. 97.
0 Disabled
1 Drain switch
2 Gas pressure
switch
Dened
by Par. 97
I General
M1 120
Prog
Input 5.
The value of this parameter is dened by Par. 97.
0 Disabled
1 T_Return
sensor
2 Extern switch
Dened
by Par. 97
I General
M1 121
Prog
Input 6.
The value of this parameter is dened by Par. 97.
0 Disabled
1 T_Flue sensor
2 Flue switch
3 APS switch
Dened
by Par. 97
I General
M1 122
Prog
Input 7.
The value of this parameter is dened by Par. 97.
0 Disabled
1 T_Flue_2
sensor
2 T_Flue_2 + Bl.
Flue
3 T_System
sensor
4 Blocked Flue
switch
5 Cascade
Sensor
Dened
by Par. 97
I General
M1 123
Prog
Input 8.
The value of this parameter is dened by Par. 97.
0 Disabled
1 T_Flue_2
sensor
2 T_Flue_2 + Bl.
Flue
3 T_System
Sensor
4 Blocked Flue
Switch
5 Cascade
Sensor
Dened
by Par. 97
I General