RECYCLING AND DISPOSAL
75
APPENDIX
APPENDIX
Menu
Par.
No.
Nr. dis-
played
Display
Description Range
Default
setting
UM
Access
type
Category
M1 139
Dair
active
Activates bleeding the system's air. To activate air
bleeding, it is necessary to switch on the boiler
and change the parameter from "No" to "Yes".
Wait for one minute. Switch off and restart. At this
stage, when it is restarted the boiler will initiate
the automatic bleeding procedure (lasting around
20 minutes). With the parameter set to "Yes", the
procedure is carried out each time the boiler is
switched off and restarted using its master switch.
The value must be set to "No" if you do not wish to
initiate the bleeding procedure when the boiler is
switched on.
Yes, No No I General
M1 140
Mini-
mum
Flow
Denes the ow rate below which the boiler is
switched off. The value varies depending on the
model.
0 - 26
(0.0 - 100)
Depends
on boiler
model
gal/
min
(l/
min)
I General
M1 107
Anti-Le-
gionella
day
Sets the weekday on which the anti-Legionella
procedure is carried out.
Sun - Sat Sun Day I DHW
M1 108
Anti-Le-
gionella
Hour
Sets the time of the day during which the anti-Le-
gionella procedure is carried out.
0 - 23 0 Hour I DHW
M2 72
Permit
Emer-
gency
Mode
Activates the emergency mode. This mode comes
on when communication between Managing and
the primary circuit's sensor is lost. In this event, if
Par. 72 is set to "Yes", the cascade is initiated, work-
ing to the xed set-point determined by Par. 74.
Yes/No Yes U Cascade
M2 74
Emer-
gency
Set-
point
Set-point active in emergency mode.
68 - 194
(20 - 90)
158 (70) °F (°C) I Cascade
M2 75
Delay
Per Start
Next
Mod.
Denes the stand-by time in seconds to restart the
subsequent cascade boiler in normal start mode.
5 - 255 120 Sec. I Cascade
M2 76
Delay
Per Stop
Next
Mod.
Denes the stand-by time in seconds to switch off
the last cascade boiler on in normal Off mode.
5 - 255 30 Sec. I Cascade
M2 142
Delay
Quick
Start
Next
Denes the stand-by time in seconds to restart the
next cascade boiler in quick start mode.
5 - 255 60 Sec. I Cascade
M2 143
Delay
Quick
Stop
Next
Denes the stand-by time in seconds to switch off
the last cascade boiler on in Quick Stop mode.
5 - 255 15 Sec. I Cascade
M2 77
Hyst.
Down
Start
Module
Denes how many degrees the temperature mea-
sured by the primary circuit's sensor must fall below
the set-point in order for the subsequent boiler to
be started after the time interval set by Par. 75.
0 - 72
(0 - 40)
9 (5) °F (°C) I Cascade
M2 78
Hyst.
Up Stop
Module
Denes by how many degrees the temperature
measured by the primary circuit's sensor must go
above the set-point in order for the subsequent
module to be switched off after the time interval
set by Par. 76.
0 - 72
(0 - 40)
7 (4) °F (°C) I Cascade
M2 144
Hyst.
Down
Quick
Start
Denes how many degrees the temperature mea-
sured by the primary circuit's sensor must go below
the set-point in order for the subsequent boiler
to be started after the time interval set by Par. 142
(quick-start mode).
0 - 72
(0 - 40)
36 (20) °F (°C) I Cascade

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Riello Array AR 399 SE and is the answer not in the manual?

Riello Array AR 399 SE Specifications

General IconGeneral
BrandRiello
ModelArray AR 399 SE
CategoryWater Heater
LanguageEnglish

Related product manuals