How to resolve WD_COMM_ERROR on Riello Array AR 4000 Boiler?
- CCynthia ArellanoSep 8, 2025
If your Riello Boiler displays a WD_COMM_ERROR, the suggested solution is to replace the power control board.

How to resolve WD_COMM_ERROR on Riello Array AR 4000 Boiler?
If your Riello Boiler displays a WD_COMM_ERROR, the suggested solution is to replace the power control board.
What to do if Riello Boiler displays HIGH_LIMIT_FAIL?
If your Riello Boiler is showing a HIGH_LIMIT_FAIL error, replace the power control board.
What to do if my Riello Boiler shows IGNIT_ERROR?
If your Riello Boiler displays the IGNIT_ERROR, several steps can be taken. First, ensure the gas supply pressure is correct and adjust if necessary. If there's no spark, check the ignition electrode position. Inspect the vent system for obstructions if the combustion air pressure is incorrect. Lastly, if the voltage to the gas valve isn't 120Vac, the power control board needs replacing.
How to troubleshoot WD_ERROR_STACK on Riello Array AR 4000?
If your Riello Boiler displays a WD_ERROR_STACK, the suggested solution is to replace the power control board.
What to do for SAFETY_RELAY_ERROR on Riello Array AR 4000?
If your Riello Boiler is showing a SAFETY_RELAY_ERROR, replace the power control board.
What does WD_ERROR_ROM mean on Riello Array AR 4000 Boiler, and how can I fix it?
If your Riello Boiler displays the WD_ERROR_ROM, the suggested solution is to replace the power control board.
How to fix WD_ERROR_RAM on Riello Array AR 4000 Boiler?
If your Riello Boiler displays a WD_ERROR_RAM, the suggested solution is to replace the power control board.
What causes E2PROM_READ_ERROR in Riello Array AR 4000 and how to fix it?
If your Riello Boiler displays the E2PROM_READ_ERROR, replace the power control board.
How to resolve FLUE_PRESSURE_ERROR on Riello Array AR 4000?
If your Riello Boiler shows a FLUE_PRESSURE_ERROR, clear any obstructions from the exhaust system. Additionally, remove any obstructions from the condensate discharge and ensure condensate can flow freely.
How to troubleshoot FAN_ERROR_NOT_RUNNING on Riello Array AR 4000 Boiler?
If your Riello Boiler is displaying the FAN_ERROR_NOT_RUNNING error, check the following: * If there's no 120 VAC voltage present, replace the power control board. * If there's no PWM signal, replace the power control board. * Replace the fan.
Introduction to the Array boilers, their features, and critical safety warnings.
Essential safety guidelines and warnings for user protection.
Critical warnings for safe installation practices and operation.
Detailed safety instructions to prevent hazards during use.
Key warnings and regulatory compliance for installation and operation.
Details on the low water protection system and its operation.
External gas regulators, specifications, and gas type conversion.
Diagrams illustrating acceptable vent and combustion air piping setups.
Details on exhaust placement and requirements for combustion air supply.
Essential checks for the gas supply before initial startup.
Step-by-step guide for safely starting the boiler.
Minimum flow protection and heating system pressure testing.
Installation and start-up procedures for cascaded boiler systems.
Accessing error logs, service reminders, and module test functions.
Normal and emergency shutdown procedures for the heating system.
Procedures for gas leak checks and system component inspections.
Detailed list of lockout codes, their causes, and solutions.
List of lockout and blocking error codes with troubleshooting steps.
Troubleshooting codes related to sensor failures or short circuits.
Troubleshooting codes for cascade system communication issues.
Minimum clearances for exhaust and air inlet terminations.
Diagrams showing acceptable vent and air intake piping arrangements.
Flowchart outlining the step-by-step burner ignition process.