EasyManua.ls Logo

Riello Condexa HPR 35 - Water Circuit

Riello Condexa HPR 35
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GENERAL REMARKS
13
2
1
4
3
Probes in the boiler
1 Safety thermostat
2 NTC delivery probe
3 Flue gas probe
4 NTC return line probe
Condexa HPR 35-45
Condexa HPR 55-70
1.11 Water circuit
2
3
8
4
5
1
7
9
10
MI
RI
6
2
3
8
5
4
1
7
9
10
MI
RI
6
Key
RI Heating return line
MI Heating delivery line
1 Degassing unit tap/boiler discharge
2 Heating pressure switch
3 Pressure transducer
4 Flow sensor
5 Safety thermostat
6 Heat exchanger
7 Return probe
8 Pressure gauge
9 Air vent valve
10 Circulator
Resistive values of the NTC probes with variations in the
temperature
Temperature °C
Tolerance test ±10%
Resistance Ω
Temperature °C
Tolerance test ±10%
Resistance Ω
-20 67523 45 4896
-15 53254 50 4147
-10 42291 55 3525
-5 33808 60 3011
0 27700 65 2582
5 22290 70 2224
10 18070 75 1922
15 14740 80 1668
20 12110 85 1451
25 10000 90 1267
30 8300 95 1110
35 6924 100 975
40 5810
2
1
4
3
Condexa HPR 35-45
Condexa HPR 55-70

Table of Contents

Related product manuals