- ENGLISH -
- 36 -
Threshold sens menu
/------------------------/
/ Threshold sens /
/------------------------/
Temperature max:100 degree C
Temperature min:20 degree C
Temp hysteresis:5 degree C
Humidity Max...:100 % RH
Humidity Min...:0 % RH
Hum hysteresis.:5 % RH
Press [Esc] to quit
With this menu is possible to set the alarm threshold for humidity and temperature sensors. When
exceeding the threshold, a SNMP alarm trap is sent. A trap is sent every minute until the alarm is
active. The alarm ceases to be active when the outbound value (temperature or humidity) is under
the threshold with the degree of hysteresis that is configured. (Example: with a maximum
temperature of 30°C and 3°C hysteresis, the alarm is activated when the temperature reaches
30°C and is removed when the temperature at 27°C).
Threshold for maximum temperature
Threshold for minimum temperature
Hysteresis for removing temperature alarm (high and low)
Threshold for maximum humidity
Threshold for minimum humidity
Hysteresis for removing humidity alarm (high and low)