RESIDENCE KIS
EN - INSTALLER AND USER MANUAL
RO - MANUAL DE INSTALARE SI UTILIZARE
HU - BESZERELÉSI ÉS FELHASZNÁLÓI KÉZIKÖNYV
EL - ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΤΗ ΚΑΙ ΧΡΗΣΤΗ
BG - РЪКОВОДСТВО ЗА ИНСТАЛИРАНЕ И ЕКСПЛОАТАЦИЯ
Question and Answer IconNeed help?

Do you have a question about the Riello RESIDENCE KIS and is the answer not in the manual?

Riello RESIDENCE KIS Specifications

General IconGeneral
Fuel TypeNatural Gas / LPG
ErP RatingA
Max Working Pressure3 bar
IgnitionElectronic
Heat Exchanger MaterialStainless Steel

Summary

1 WARNINGS AND SAFETY

General Safety Warnings and Installation Notes

Crucial safety guidelines, user restrictions, and installation precautions for safe operation and maintenance.

2 INSTALLATION MANUAL

3 INSTALLATION

Detailed procedures for installing the boiler, including system checks and connections.

3.1 Cleaning the system and characteristics of the water

Ensuring proper system function by cleaning and checking water parameters.

3.2 Dimensions and weights (fig. 5)

Provides technical specifications for boiler dimensions and weights.

3.3 Handling (Fig. 6)

Instructions for manually handling the boiler after unpacking.

3.4 Installation room

3.5 Installation on appliances that are old or that need to be updated

Checks required when installing on older or updated systems.

3.6 Installation regulations

Compliance with relevant standards for boiler installation.

ANTI-FREEZE SYSTEM

Explanation of the standard automatic anti-freeze system and its limitations.

3.7 Installation of condensate drain pipe (Fig. 9)

3.8 Instruction for condensation exhaust connection

Details on connecting the condensation exhaust system to prevent gas escape.

3.9 Positioning the wall-mounted boiler and hydraulic connections (Fig. 10)

3.10 Electrical connections

Guidance on making low voltage and high voltage electrical connections.

3.11 Gas connection

Procedure for connecting the gas supply, ensuring correct gas type.

3.12 Variable speed circulator

Explanation of the different operating modes for the variable speed circulator.

3.12 Variable speed circulator

EXCEPTIONAL USE OF A STANDARD CIRCULATOR WHOSE SPEED CANNOT BE RE- GULATED (P4.05 = 0)

Guidance on using a traditional circulator in exceptional cases.

3.13 Manual reset of the circulator

Procedure for performing a manual reset on the circulator.

3.14 Removing the casing

Step-by-step guide to safely remove the boiler casing for access.

3.15 Flue gas exhaust and combustion air suction (Fig. 12)

Requirements for flue gas evacuation and combustion air intake.

3.15 Flue gas exhaust and combustion air suction (Fig. 12)

Twin pipes with Ø 80 pipework (Ø50 - Ø60 - Ø80) (Fig. 17)

Guidance on using Ø80 flue gas exhaust pipe with different piping ranges.

3.16 Installation on collective flues in positive pressure (fig 18)

Guidelines for installing the boiler on collective flues in positive pressure systems.

3.17 Filling the heating system and eliminating air

3.18 Draining the heating system

Instructions for safely draining the heating system.

3.19 Emptying the domestic hot water circuit

Procedure for emptying the domestic hot water circuit to prevent frost damage.

3.20 Condensate siphon

Explanation of the condensate siphon's function and maintenance.

3.21 Control panel

SETTINGS MENU TREE STRUCTURE

P1 (SETTINGS menu)

Parameters for interface settings like language, time, and scrolling text.

P2 (COMBUSTION menu)

Parameters related to gas type, boiler type, and combustion settings.

P3 (CONFIGURATION menu)

Settings for hydraulic configuration, water pressure, and air purging.

P4 (HEATING menu)

P4.16 MAX CH SET

Parameter to set the maximum heating setpoint.

P4.17 MIN CH SET

Parameter to set the minimum heating setpoint.

P4.18 WEATHER COMP ENABLE

Parameter to activate weather compensation.

P4.19 WEATHER COMP CURVE

Parameter to set the weather compensation curve.

P4 (HEATING menu)

P4.27 ZONE1 SET

Parameter to set the heating setpoint for zone 1.

P4.28 ZONE1 MAX CH SET

Parameter to set the maximum heating setpoint for zone 1.

P4.29 ZONE1 MIN CH SET

Parameter to set the minimum heating setpoint for zone 1.

P5 (DHW menu)

P8 (CONNECTIVITY menu)

4 COMMISSIONING

4.1 Preliminary checks

Essential checks to perform before the first ignition and startup.

4.2 Programming the boiler

Steps for setting the time, day, and language of the boiler's control interface.

4.2 Programming the boiler

Vent cycle

Description of the automatic vent cycle performed on boiler startup.

4.3 Boiler configuration

Detailed explanation of boiler configuration parameters and their settings.

4.3 Boiler configuration

P4 (HEATING menu)

Parameters for heating system control, including hysteresis and pump settings.

P4.16 MAX CH SET

Parameter to set the maximum heating setpoint.

P4.17 MIN CH SET

Parameter to set the minimum heating setpoint.

P4.18 WEATHER COMP ENABLE

Parameter to activate weather compensation.

P4.19 WEATHER COMP CURVE

Parameter to set the weather compensation curve.

4.4 Setting the thermoregulation

Offset on the reference ambient temperature (fig. 20)

Adjusting the heating setpoint offset relative to the reference temperature.

NIGHT COMPENSATION (parameter P4.20 - fig. 20)

Enabling and setting night compensation via the P4.20 parameter.

REQUEST FROM OT CHRONOTHERMOSTAT

How the delivery setpoint is calculated with an OT chronostat.

REQUEST FROM ROOM THERMOSTAT

How the delivery setpoint is calculated with a room thermostat.

Selecting the thermoregulation curve (parameter P4.19 - fig. 20)

Choosing the appropriate compensation curve for thermoregulation.

4.5 First commissioning

4.6 Operating status

WINTER MODE

Setting the boiler to WINTER status for heating and hot water.

SUMMER MODE

Setting the boiler to SUMMER status for domestic hot water only.

OFF

Setting the boiler to OFF status.

4.7 Adjusting the heating water temperature without an outdoor temperature sensor connected

4.8 Adjusting the heating water temperature with an outdoor temperature sensor connected

4.9 Adjusting the domestic hot water temperature

4.10 Safety stop

4.11 Reset function

4.12 Domestic hot water comfort function

CSTD (PREHEATING function)

Activating the preheating function for domestic hot water.

CSMT (TOUCH&GO function)

Activating the Touch&Go function for on-demand hot water preheating.

4.13 Special domestic hot water functions

4.14 Screed heating function

4.16 Combustion check

Set the maximum desired heating value (rpm)...

Instruction for setting the maximum heating output value.

4.17 Gas conversion

4.18 Range rated

Set the maximum desired heating value (rpm)...

Instruction for setting the maximum heating output value.

4.19 Lights and faults

Reset function

Procedure for resetting the boiler after a fault.

4.19 Lights and faults

For fault E041

Explanation of fault code E041 related to low pressure.

For fault E060

Explanation of fault code E060 related to DHW temperature stability.

For fault E091

Explanation of fault code E091 related to primary heat exchanger cleaning.

4.20 INFO menu

4.21 Temporary switch-off

4.22 Switching off for lengthy periods

4.23 Keyboard lockout function

4.24 Interface Stand by

4.25 Replacing interface

4.26 Replacing the board

4.27 Combustion Control Parameters

5 MAINTENANCE AND CLEANING

Cleaning the primary heat exchanger (Fig. 21)

Detailed steps for cleaning the primary heat exchanger.

Cleaning the burner (Fig. 21):

Detailed steps for cleaning the boiler's burner.

Cleaning the siphon

Instructions for cleaning the condensate siphon and SRD device.

Maintenance of the ionisation electrode

Proper maintenance and replacement of the ionisation electrode.

Check valve (Fig. 22)

Procedure for accessing and checking the boiler's check valve.

Removing the siphon (Fig. 23a-b-c-d)

Step-by-step guide to removing the siphon and its components.

5 MAINTENANCE AND CLEANING

If, after replacing the electronic board or having carried out maintenance on the detector electrode...

Note regarding combustion parameter variations after electrode maintenance.

Do not clean the appliance or its parts with inflammable substances...

Safety warning against using flammable cleaning agents.

Panel cleaning must be carried out only with soapy water.

Instruction for cleaning panels using only soapy water.

TECHNICAL DATA

Heating

Technical data related to the heating function of the boiler.

DHW

Technical data related to the domestic hot water (DHW) function.

For combination heaters

Technical data specifically for combination heater functionality.

Serial number plate

Information located on the boiler's serial number plate.

TECHNICAL DATA

Hydraulic connections

Specifications for the boiler's hydraulic connections.

Domestic hot water capacity

Data related to the domestic hot water capacity.

Fan performance

Performance data for the boiler's fan.

Concentric flue gas outlet pipes

Specifications for concentric flue gas outlet pipes.

Forced open installation B23P-B53P

Specifications for forced open installation configurations.

Emission values at maximum and minimum output (**)

Boiler emission values for different operating outputs.

TECHNICAL DATA

CH maximum gas capacity

Maximum gas capacity for central heating.

DHW maximum gas capacity

Maximum gas capacity for domestic hot water.

CH minimum gas capacity

Minimum gas capacity for central heating.

DHW minimum gas capacity

Minimum gas capacity for domestic hot water.

Number of fan rotations with slow ignition

Fan rotation speed during slow ignition.

Maximum number of CH fan rotations

Maximum fan rotation speed for central heating.

Maximum number of DHW fan rotations

Maximum fan rotation speed for domestic hot water.

Minimum number of CH/DHW fan rotations

Minimum fan rotation speed for CH/DHW.

TECHNICAL DATA

Seasonal space heating energy efficiency class

Energy efficiency class for space heating.

Water heating energy efficiency class

Energy efficiency class for water heating.

Rated heat output

The maximum heat output of the boiler.

Seasonal space heating energy efficiency

The energy efficiency of the boiler for space heating.

Useful heat output

The useful heat output of the boiler.

Useful efficiency

The useful efficiency of the boiler for different operating conditions.

Auxiliary electricity consumption

Electricity consumption of the boiler in different operating states.

Other parameters

Additional technical parameters of the boiler.

For combination heaters

Technical data specifically for combination heater modes.

Serial number plate

Information located on the boiler's serial number plate.

6-metre circulator (factory setted) / pompă de circulaţie de 6 metri (setare din fabrică) / 6 méteres keringtető szivattyú (gyári beállítás) / Κυκλοφορητής 6 μέτρων (ρυθμισμένος από το εργοστάσιο) / Циркулационна помпа 6 метра (фабрично монтирана)

[EN] - Residual head of circulator

Explains the circulator's performance curve and anti-blocking function.

7-metre circulator (accessory) / pompă de circulaţie de 7 metri (accesoriu) / 7 méteres keringtető szivattyú (tartozék) / Βασικός κυκλοφορητής 7 μέτρων (αξεσουάρ) / Циркулационна помпа 7 метра (опция)

MAX LENGTH PIPES Ø80 + Ø80

[EN] MAX LENGTH PIPES Ø80 + Ø80

Graphs showing maximum flue and air pipe lengths based on bends and system configuration.

[EN] THERMOREGULATION CURVES

A GRAPHIC 1 - THERMOREGULATION CURVES

Graphs illustrating different thermoregulation curves for heating control.

B GRAPHIC 2 - CLIMATE CURVE CORRECTION

Graphs for correcting the climate curve based on external factors.

C GRAPHIC 3 - PARALLEL NIGHT TIME REDUCTION

Graphs showing parallel night time reduction for heating.

D EXTERNAL TEMPERATURE (°C)

X-axis label: External temperature in degrees Celsius.

E DELIVERY TEMPERATURE (°C)

Y-axis label: Delivery temperature in degrees Celsius.

F DAY TEMPERATURE CURVE

Graph illustrating the day temperature curve for heating.

G NIGHT TEMPERATURE CURVE

Graph illustrating the night temperature curve for heating.

T80 Maximum temperature heating setpoint for std systems

Setpoint for maximum heating temperature in standard systems.

T45 Maximum temperature heating setpoint for floor systems

Setpoint for maximum heating temperature in floor systems.