EasyManua.ls Logo

Rinnai Circ-Logic Series - Troubleshooting; Sequence of Operation

Rinnai Circ-Logic Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 Rinnai Circ-Logic™ with Grundfos Kit
Troubleshoong
When the pump is rst started, the sha may rotate
slowly unl water has fully penetrated the bearings. If
the pump does not run, the sha can be rotated
manually. To accomplish this, switch o the electrical
supply, and close the isolaon valves on each side of
the pump. Remove the large screw in the middle of
the nameplate. Insert a small at blade screwdriver
into the end of the sha, and gently turn unl the
sha moves freely (see Figure 8). Replace and ghten
the plug. Open the isolaon valves and wait 2 to 3
minutes for the system pressure to equalize before
starng the pump. (See Figure 8)
For technical assistance, please contact Rinnai at
1-866-RINNAI1 (746-6241).
Sequence of Operaon
A. When the manual switch of the Grundfos mer is
in the “ON “ posion, the Cir-Logic™ will control
the pump.
B. When the manual switch is in the “TIMER” posi-
on:
- if the mer output relay is
acvated
the Cir-
Logic™ will control the pump.
- if the mer output relay is
deacvated
the pump
will remain o.
C. When the manual switch is in the “OFF posion
the pump will not run.
Sequence of Operaons Flowchart
Figure 8
NOTE
The isolation valves are to be field supplied. This image
is just for illustration purposes only.

Related product manuals