24 Rittal PDU metered/metered plus/switched/managed
2 Safety instructions
Assembly and installation of the device may only be performed by experienced, trained specialists.
The PDU housing must not be opened.
The PDU must not come into contact with water, aggressive or inflammable gases or vapours.
The PDU may only be operated within the specified environmental conditions (see section 8.1).
The PDU is connected permanently to the mains power and does not have a main switch for the all-
pole mains power decoupling.
Attention: The occurrence of a high touch current is possible, because the protective-conductor cur-
rent can lie above 5 mA by summation of the protective-conductor currents of the connected units.
Consequently, the unit must always be connected to the protective-earth conductor of the building's
electrical system.
3 Product description
3.1 Functional description
The PDU is a power distribution unit for use in IT racks. There are four design variants, with the following
distinguishing features:
PDU metered: Energy measurement at the infeed per phase, i.e. output requirement of an entire
IT rack; no switching function; with display and network interface.
PDU metered plus: energy measurement at each individual outlet socket; no switching function; with
display and network interface.
PDU switched: Energy measurement at the infeed per phase, i.e. output requirement of an entire
IT rack; with switching function per individual output slot, display and network interface.
PDU managed: Energy measurement and switching function per individual output slot; with display
and network interface.
3.2 Intended use
The PDU is used, in particular, for distributing power in IT racks and is envisaged for permanent instal-
lation in IT racks. It must not be used at locations where children may be present and is envisaged for
use only in a restricted access area (e.g. lockable rack).
3.3 Operating conditions
The PDU may be operated only under the operating conditions listed in section 8 "Technical specifica-
tions".
Note:
Further safety instructions in all EU languages can be found on page 2 to 4.
Safety instructions, Product description

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rittal PDU metered Series and is the answer not in the manual?

Rittal PDU metered Series Specifications

General IconGeneral
BrandRittal
ModelPDU metered Series
CategoryPower distribution unit
LanguageEnglish