32 Rittal PDU metered/metered plus/switched/managed
8 Technical specifications
8.1 General technical specifications
8.2 Identification keys for model variants
PDU-A-B-C-D-50/60Hz-E-F-G-H-I-J
Technical specifications
Temperature application range: Temperature Operation: +5 °C…+50 °C (at 100% load))
Temperature Storage: -20 °C…+70 °C
Humidity application range: 10%…95% relative humidity, non-condensing
Protection category: IP 20 to IEC 60 529
Protection class: 1
Overvoltage category: II
Degree of contamination: 2
max. operating height: 3,000 meters above sea level
min. operating time: 100,000 h
EU conformity: Low-Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
IEC/EN 62368
Input voltage range (L – N) 90 V…260 (400) V AC, 50…60 Hz
Input current 16 A/32 A (depending on variant)
No. of phases 1 or 3 depending on PDU variant
Colour coding of the phases/fuse circuits (3-phase ver-
sions only):
L1: pink
L2: black
L3: white
Connection cable type H05-VV
No. of wires 3/5 (single-phase/3-phase PDU)
Type Electrical
design
Supply
cord
Add-on
supply
Add-on
per
phase
Add-on
per fuse
Fuse
breaking
capacity
Quantity of
sockets
-A- -B- -C- -D- -E- -F- or
blank
-G- or
blank
-H- or
blank
-I- or
blank
-J-
Metered L/N/PE 230 V 32 A E2=
1 m
F2=RCD G2=RCD H2=RCD I2=10 kA J2=2
Metered
Plus
L1/L2/L3/N/PE 400 V 16 A E3=
1,5 m
F3=RCM G3=RC
M
H3=RC
M
J3=3
Switched L1/L2/L3/N/PE 400 V 32 A F4=OPD
&RCD
G4=OPD
&RCD
H4=OPD
&RCD
Managed L1/L2/L3/N/PE 400 V 32 A E24=
12 m
F5=OPD
&RCM
G5=OPD
&RCM
H5=OPD
&RCM
J52=
52
Technical specifications