65-2340RKSS Toxic Gas Transmitter 5
Installation
This section describes procedures to mount the toxic gas transmitter in the monitoring
environment and wire the transmitter to a controller.
Mounting the Toxic Gas Transmitter
1. Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.
Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.
Select a site where the target gas is likely to be found first.
Figure 3: Mounting the Toxic Gas Transmitter
Text Oriented
This Way
3.15
2.40
3/4 NPT
Conduit Hub
.20 Dia. x .45
Slot, 2X
Toxic
Detector
Junction
Box
10.00 Max
1.10