RS485 (DSI) Protocol C-3
Writing (06) Logic Command Data
The PowerFlex 4 drive can be controlled via the network by sending
Function Code 06 writes to register address 8192 (Logic Command).
P036 [Start Source] must be set to 5 “RS485 (DSI) Port” in order to
accept the commands.
Writing (06) Reference
The Speed Reference to a PowerFlex 4 drive can be controlled via the
network by sending Function Code 06 writes to register address 8193
(Reference). P038 [Speed Reference] must be set to 5 “RS485 (DSI)
Port” in order to accept the Speed Reference.
Logic Command
Address (Decimal) Bit(s) Description
8192
0 1 = Stop, 0 = Not Stop
1 1 = Start, 0 = Not Start
2 1 = Jog, 0 = No Jog
3 1 = Clear Faults, 0 = Not Clear Faults
5,4
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Change Direction (Toggle)
6 Not Used
7 Not Used
9,8
00 = No Command
01 = Accel Rate 1 Enable
10 = Accel Rate 2 Enable
11 = Hold Accel Rate Selected
11,10
00 = No Command
01 = Decel Rate 1 Enable
10 = Decel Rate 2 Enable
11 = Hold Decel Rate Selected
14,13,12
000 = No Command
001 = Freq. Source = P036 [Start Source]
010 = Freq. Source = A069 [Internal Freq]
011 = Freq. Source = Comms (Addr 8193)
100 = A070 [Preset Freq 0]
101 = A071 [Preset Freq 1]
110 = A072 [Preset Freq 2]
111 = A073 [Preset Freq 3]
15 Not Used
Reference
Address (Decimal) Description
8193
A decimal value entered as xxx.x where the decimal point is xed. For
example, a decimal 100 equals 10.0 Hz and 543 equals 54.3 Hz.