Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 15
Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual
EMC The electromagnetic capability (EMC) behavior of the device is designed for
applications in the industrial environment and residential, commercial, and
light industry environments.The device is investigated according to EN 61000-
6-1, EN 61000-6-2, EN 61000-6-3, and EN 61000-6-4.
EMC Immunity
Electrostatic discharge EN 61000-4-2
Contact discharge 8 kV
Criterion A
(1)
(1) A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device can shut down and restarts by itself. No damage or hazards for the
device will occur.
Air discharge 15 kV Criterion A
Electromagnetic RF field EN 61000-4-3 80 MHz…2.7 GHz 20V/m Criterion A
Fast transients (Burst) EN 61000-4-4
Input lines Output lines 4 kV Criterion A
Output lines 2 kV Criterion A
DC OK signal (coupling
clamp)
2 kV Criterion A
Surge voltage on input EN 61000-4-5
L to N, 2 kV Criterion A
L to PE, N to PE 4 kV Criterion A
Surge voltage on output EN 61000-4-5
+ to - 1 kV Criterion A
+/- to PE 2 kV Criterion A
Surge voltage on DC OK EN 61000-4-5 DC Okay Signal to PE 1 kV Criterion A
Conducted disturbance EN 61000-4-6
0.15…80 MHz 20V Criterion A
0% of 100V AC 0V AC, 20 ms Criterion A
40% of 100V AC 40V AC, 200 ms Criterion C
70% of 100V AC 70V AC, 500 ms Criterion A
0% of 100V AC 0V AC, 20 ms Criterion A
40% of 100V AC 80V AC, 200 ms, < 4 A Criterion A
40% of 100V AC 80V AC,500 ms, > 4 A Criterion C
70% of 100V AC 140V AC, 20 ms Criterion A
Voltage interruptions EN 61000-4-11 0% of 200V AC (=0V) 5000 ms Criterion C
Powerful transients VDE 0160 Over entire load range 750V, 0.3 ms Criterion A
EMC Emission
Conducted emission input lines EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B
Conducted emission output lines IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Limits for local DC power networks fulfilled
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current (PFC) EN 61000-3-2 Fulfilled for Class A equipment
Voltage fluctuations, flicker EN 61000-3-3
Fulfilled, tested with constant current loads, non-
pulsing
This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device cannot cause harmful interference, and (2) this device must
accept any interference received, including interference that can cause undesired operation.
Switching Frequency
PFC converter 110 kHz Fixed frequency
Main converter 84 kHz …140 kHz Output load dependent
Auxiliary converter 60 kHz Fixed frequency