16 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020
Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual
Environment
Operational
temperature
-25 …+70 °C (-13…158 °F)
Operational temperature is the same as the ambient or surrounding temperature
and is defined as the air temperature 20 mm (0.79 in.) below the unit
Storage temperature - 40 °C…+85 °C (-40 °F…185 °F) For storage and transportation
Output de-rating
.6 W/1 °C (1.6 W/1.8 °F)
45 °C…60 °C (113 °F…140 °F)
3 W/1 °C (3 W/1.8 °F)
60 °C…70 °C (140 °F…158 °F)
0.33A/1000 m or 5 °C/1000 m For altitudes >2000 m (6560 ft), see Figure 25
The de-rating is not hardware that is controlled. The user has to take this into consideration to stay below the de-rated current limits in order not
to overload the unit.
Humidity 5...95% r.h. According to IEC 60068-2-30
Atmospheric pressure 110…54 kPa See Figure 25
for details
Altitude Up to 5000 m (16,400 ft) See Figure 25
for details
Overvoltage category
III According to IEC 60664-1 for altitudes up to 2000 m (6560 ft)
II According to IEC 60664-1 for altitudes above 2000 m (6560 ft)
Degree of pollution 2 According to IEC 62477-1, not conductive
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2 g 2 hours/axis According to IEC 60068-2-6
Shock
30 g 6 ms, 20 g 11 ms 3 bumps per direction, 18 bumps in total According to IEC 60068-2-27
Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm (0.59 in.) and a thickness of 1.3 mm
(0.05 in.) and standard orientation.
LABS compatibility As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is suitable for use in paint shops.
Corrosive gases
Tested according to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a service life of minimum 10 years in these
environments.
Audible noise Some audible noise can be emitted from the power supply during no load, overload, or short circuit.
Figure 24 - Output Current Versus Ambient Temperature Figure 25 - Output Current Versus Altitude
Allowed Output Current at 24V
0
-25 0
45
70°C
3.8 A
5 A
6 A
60
A
Ambient Temperature
A... 85 to 264V AC, continuous
B... short term
B
2000 m
5000 m
4 A
5 A
6 A
A
ltitude
Allowed Output Current at 24V
B
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
4
5
°
C
C
.
.
.
Short term
A
C
A
P
*
80 kPa
54 kPa110 kPa
0m
* Atmospheric pressure

Related product manuals