Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 7
Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual
AC Input The device is suitable to be supplied from TN, TT, or IT mains networks with
AC voltage. For suitable DC supply voltages,
See DC Input on page 8.
Attribute Value Notes
AC input Nom AC 100-240V
AC input range
Min 85-264V AC Continuous operation
Min 264-300V AC Occasionally for maximal 500 ms
Allowed voltage L or N to earth Max 300V AC Continuous, according to IEC 60664-1
Input frequency Nom 50…60 Hz ±6%
Turn-on voltage Typ 80V AC Steady-state value, see
Figure 1
Shut-down voltage Typ 74V AC Steady-state value, see Figure 1
External input protection See Installation Instructions on page 6.
AC 100V AC 120V AC 230V
Input current Typ 1.30 A 1.09 A 0.60 A At 24V, 5 A, see Figure 3
Power factor Typ 0.99 0.98 0.91 At 24V, 5 A, see Figure 4
Crest factor Typ 1.7 1.8 2.2
At 24V, 5 A, The crest factor is the mathematical ratio of the peak value to RMS value of the input current
waveform.
Startup delay Typ 420 ms 380 ms 385 ms See Figure 2
Rise time
Typ 80 ms 80 ms 80 ms At 24V, 5 A constant current load, 0 mF load capacitance, see Figure 2
Typ 100 ms 100 ms 110 ms At 24V, 5 A constant current load, 5 mF load capacitance, see Figure 2
Max 200 mV 200 mV 200 mV See Figure 2
Figure 1 - Input Voltage Range Figure 2 - Turn-on Behavior, Definitions
Figure 3 - Input Current Versus Output Current at 24V Output Voltage Figure 4 - Power Factor Versus Output Current at 24V Output Voltage