6 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020
Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual
Specifications
Catalog Numbers
Terminology and
Abbreviations
Attribute Value Notes
Output voltage 24V DC Nominal
Adjustment range 24…28V Factory setting 24.1V
Output current
6.0…5.1 A Below 45 °C (113 °F) ambient
5.0…4.3 A At 60 °C (140 °F) ambient
3.8…3.2 A
Derate linearly 45…70 °C (113…158 °F)
Input voltage AC AC 100…240V -15%/+10%
Mains frequency 50…60 Hz ±6%
Input current AC 1.09/0.6 A At 120/230V AC
Power factor 0.98/0.91 At 120/230V AC
Input voltage DC
DC 110…150V
±20%
For 1606-XLE120E, 1606-XLE120EC, 1606-XLE120EL,
1606-XLE120EH
DC 110…300V
±20%
For 1606-XLE120ED
Input current DC 1.21/0.43 A At 110/300V DC
AC Inrush current 4/4 A At 120/230V AC
Efficiency 93.6/94.3% At 120/230V AC
Losses 8.2/7.3 W At 120/230V AC
Hold-up time 35/35 ms At 120/230V AC
Temperature range -25…+70 °C (-13…+158 °F)
Size (WxHxD) 32x124x102 mm (1.26x4.88x4.02 in.) Without DIN rail
Weight 440 g (0.97 lb)
Power Supply Connection
1606-XLE120E Screw terminals
1606-XLE120EC Screw terminals and conformal coated pc-boards
1606-XLE120EL Spring-damp terminals
1606-XLE120EH Push-in terminals
1606-XLE120ED Screw terminals and enhanced DC input
Term Definition
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol.
Earth, Ground This document uses the term ‘earth’ which is the same as the U.S. term ‘ground.’
AC 230V
A figure that is displayed with the AC or DC before the value represents a nominal voltage
with standard tolerances (usually ±15%) included. For example: DC 12V describes a 12V
battery disregarding whether it is full (13.7V) or flat (10V).
230V AC
A figure with the unit (V AC) at the end is a momentary figure without any additional
tolerances included.
50 Hz vs. 60 Hz As long as not otherwise stated, AC 230V parameters are valid at 50 Hz mains frequency.