16 ControlLogix Power Supplies
Publication 1756-IN613A-EN-P - December 2008
Wire category
1
(5)
on power ports
North American temp code T4
Mounting screw torque 0.8 N•m (7 lb•in)
(1)
The combination of all output power (1.2V, 3.3V, 5.1V, and 24V) cannot exceed 75 W.
(2)
The hold up time is all the time between input voltage removal and DC power failure.
(3)
Use time-delay type overcurrent protection in all ungrounded conductors.
(4)
This fuse is intended to guard against fire hazard due to short circuit conditions.
(5)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
1756-PA72 Series C, 1756-PA75 Series B - Environmental Specifications
Attribute 1756-PA72 Series C 1756-PA75 Series B
Operating temperature
IEC 60068-2-1 (Test Ad, Operating
Cold)
IEC 60068-2-2 (Test Bd, Operating
Dry Heat)
IEC 60068-2-14 (Test Nb,
Operating Thermal Shock)
0…60 °C (32…140 °F)
Nonoperating temperature
IEC 60068-2-1 (Test Ab,
Unpackaged Nonoperating Cold)
IEC 60068-2-2 (Test Bb,
Unpackaged Nonoperating Dry
Heat)
IEC 60068-2-14 (Test Na,
Unpackaged Nonoperating
Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db,
Unpackaged Nonoperating Damp
Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Operating shock
IEC 60068-2-27 (Test Ea,
Unpackaged Shock)
30 g
Nonoperating shock
IEC 60068-2-27 (Test Ea,
Unpackaged Shock)
50 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
1756-PA72 Series C, 1756-PA75 Series B - Technical Specifications
Attribute 1756-PA72 Series C 1756-PA75 Series B