EasyManua.ls Logo

Rolls Battery - Capacity Increase Example; Combined Voltage;Capacity Increase

Rolls Battery
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
To increase capacity, connect the batteries in parallel as shown in Figure 2.
EXAMPLE:
Battery Voltage = 6V each
Battery Capacity = 400 AH each
System Voltage = 6V
System Capacity = 800 AH
To increase capacity and voltage, connect the batteries in series parallel as shown in Figure 3.
EXAMPLE:
Battery Voltage = 6V each
Battery Capacity = 400 AH each
System Voltage = 12V
System Capacity = 800 AH
EXAMPLE:
twenty four (24) 2 Volt 2YS31P models at 2430 AH each = 2430AH at 48 Volts
EXAMPLE:
two (2) strings of eight (8) 6 Volt S-530 models at 400 AH each = 2 x 400 AH at 48
Volts = 800 AH at 48 Volts
EXAMPLE:
three (3) strings of four (4) 12 Volt 12CS11P models at 357 AH each = 3 x 357 AH at
48 Volts = 1071 AH at 48 Volts
NOTE: We do not recommend more than three (3) series strings. Multiple parallel
connection create unequal string resistances, resulting in possible cell damage or failure.
4
Figure 2
Capacity Increase
Figure 3
Voltage/Capacity Increase
Figure 4
Single Series String
“Best Setup”
Figure 6
Three Series String
Figure 5
Two Series String
- +
-
-
-
++ + + + + + + + + + ++
+ + + + + + +++++
-
- - - ---- - - --
- - - - - - - - - - --
+
-
++ + + + + + ++
- --- - - --
- - - - - - --
+ + + + + + +
+
-
++ + ++
- - --
- - --
+ + + +
- - --
+ + + +
+
+
++
-
-
-
-
+
-
+
-