11 Maintenance and service
Installation and operation manual
30
RHYKOMB33AA
ROTEX HPU hybrid gas boiler module
4P353068-1B – 2014.02
9 Lift the condensate drain pan on the left-hand side from the
connection to the condensate trap.
10 Turn it to the right with the condensate trap connection over the
edge of the base tray.
11 Push the backside of the condensate drain pan downwards
from the connection to the heat exchanger and remove it.
12 Remove the connector from the fan and the ignition unit from
the gas valve.
13 Unscrew the coupling below the gas valve.
14 Unscrew the socket head screws from the front cover and
remove the socket complete with gas valve and fan to the front.
NOTICE
Make sure that the burner, insulation plate, gas valve, gas
supply and fan do NOT get damaged.
11.3 To clean the inside of the gas
boiler
1 Clean the heat exchanger from top to bottom with a plastic
brush or compressed air.
2 Clean the underside of the heat exchanger.
3 Clean the condensate drain pan with water.
4 Clean the condensate trap with water.

Table of Contents

Other manuals for Rotex RHYKOMB33AA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotex RHYKOMB33AA and is the answer not in the manual?

Rotex RHYKOMB33AA Specifications

General IconGeneral
BrandRotex
ModelRHYKOMB33AA
CategoryBoiler
LanguageEnglish

Related product manuals