1Ø2W DIRECT
CONNECTION
264-1019
264-1019 Instrucon Manual
All terminal covers must be
ed and secured with
sealing hasp.
RTU
Safety related nocaon, symbols and instrucons that appear in this
operang manual or on the equipment must be strictly followed to
ensure the safety of personnel as well as the instrument. If the
equipment is not used in a manner specied by the manufacturer it may
impair the protecon provided by the equipment
Do not use the equipment if there are mechanical damage
Do not exceed the stated maximum rangs of the device
No repairs, maintenance or adjustments are possible
Read the complete instrucon manual prior to installaon or
operang the unit
The equipment in its installed state must not come into close
proximity to any heang sources, oils, steam, causc vapours or
other unwanted process by-products
Do not use in hazardous or classied locaon where explosion or
other dangers can be triggered by the device
PRODUCT SAFETY
INSTALLATION PRECAUTIONS
Risk of electric shock!
Only to be installed by a competent person
To prevent the risk of electrocuon, always isolate and lock-o the
power supply to the equipment prior to undertaking any work
Always conrm absence of electricity prior to starng work using
appropriate voltage detecon equipment
Wiring shall be done strictly according to the terminal layout
Conrm that all connecons are correct before energizing the
equipment
Roung of cables shall be way from any internal EMI source
Copper cable should be used
All wiring to be in accordance with applicable local standards
Installaon must comply
with MID cered
requirements
Specicaons Accuracy
Wiring Input
1Ø 2 wire Voltage V
L-N
±0.5% of full scale
Rated Input Voltage 230V AC ±20% Current ±0.5% of full scale
Frequency Range 50 or 60Hz (MID approved @ 50Hz) Frequency for L-N > 20V, L-L > 35V ±0.1% of full scale
Rated Input Current Ib = 10A, Imin = 0.5A, Imax = 100A Acve, Reacve and Apparent Power 1% of full scale
Power Consumpon < 8VA Power Factor ±0.01 of Unity
Display Update Rate 1 sec all parameters Acve Energy EN50470-3: Cl.B
Operang / Storage Temperature -10…55°C / -20…75°C Reacve Energy EN62053-23: Cl.2
Humidity 0...85% non-condensing Apparent Energy Class 1
Protecon Degree (IEC/EN60529) IP54 (front of Housing), IP20 (terminals)
Pulse Output voltage range /
Max Current
Volt-free - require external 5...24V DC
100mA max
Pulse Resoluon
1: 1000 pulses/kWh (Fixed)
2: 1/10/100/1000 pulses/kWh or
pulses/kVArh (congurable)
Pulse Duraon 0.05...2 sec (congurable)
EO&E: Document subject to change
Modbus (RI-D35-100-C Only)
Interface Standard & Protocol RS485 / Modbus RTU
Communicaon Address 1...255
Transmission Mode Half Duplex
Data Type FLOAT & INTEGER
Transmission distance 500m max
Transmission Speed 9600 / 19200 bps
Parity None / Odd / Even
Stop Bits 1 / 2