264-1019-IM-V02
1
1Ø2W DIRECT
CONNECTION
264-1019
264-1019 Instrucon Manual
All terminal covers must be
ed and secured with
sealing hasp.
RTU
Safety related nocaon, symbols and instrucons that appear in this
operang manual or on the equipment must be strictly followed to
ensure the safety of personnel as well as the instrument. If the
equipment is not used in a manner specied by the manufacturer it may
impair the protecon provided by the equipment
• Do not use the equipment if there are mechanical damage
• Do not exceed the stated maximum rangs of the device
• No repairs, maintenance or adjustments are possible
• Read the complete instrucon manual prior to installaon or
operang the unit
• The equipment in its installed state must not come into close
proximity to any heang sources, oils, steam, causc vapours or
other unwanted process by-products
• Do not use in hazardous or classied locaon where explosion or
other dangers can be triggered by the device
PRODUCT SAFETY
INSTALLATION PRECAUTIONS
Risk of electric shock!
Only to be installed by a competent person
• To prevent the risk of electrocuon, always isolate and lock-o the
power supply to the equipment prior to undertaking any work
• Always conrm absence of electricity prior to starng work using
appropriate voltage detecon equipment
• Wiring shall be done strictly according to the terminal layout
• Conrm that all connecons are correct before energizing the
equipment
• Roung of cables shall be way from any internal EMI source
• Copper cable should be used
• All wiring to be in accordance with applicable local standards
Installaon must comply
with MID cered
requirements
Specicaons Accuracy
Wiring Input
1Ø 2 wire Voltage V
L-N
±0.5% of full scale
Rated Input Voltage 230V AC ±20% Current ±0.5% of full scale
Frequency Range 50 or 60Hz (MID approved @ 50Hz) Frequency for L-N > 20V, L-L > 35V ±0.1% of full scale
Rated Input Current Ib = 10A, Imin = 0.5A, Imax = 100A Acve, Reacve and Apparent Power 1% of full scale
Power Consumpon < 8VA Power Factor ±0.01 of Unity
Display Update Rate 1 sec all parameters Acve Energy EN50470-3: Cl.B
Operang / Storage Temperature -10…55°C / -20…75°C Reacve Energy EN62053-23: Cl.2
Humidity 0...85% non-condensing Apparent Energy Class 1
Protecon Degree (IEC/EN60529) IP54 (front of Housing), IP20 (terminals)
Pulse Output voltage range /
Max Current
Volt-free - require external 5...24V DC
100mA max
Pulse Resoluon
1: 1000 pulses/kWh (Fixed)
2: 1/10/100/1000 pulses/kWh or
pulses/kVArh (congurable)
Pulse Duraon 0.05...2 sec (congurable)
EO&E: Document subject to change
Modbus (RI-D35-100-C Only)
Interface Standard & Protocol RS485 / Modbus RTU
Communicaon Address 1...255
Transmission Mode Half Duplex
Data Type FLOAT & INTEGER
Transmission distance 500m max
Transmission Speed 9600 / 19200 bps
Parity None / Odd / Even
Stop Bits 1 / 2