MODELF67Q/F71Q/F68Q/F69Q/F116Q/F117Q
43
3.4 Parameter settlement
Service Time T1
Water Treatment Capacity:
Q=V
R
×K÷Y
D
(m
3
)
Hardness of Inlet Water, mmol/L.
Exchange factor, mmol/L, 4001000.
Down-flow regeneration, take 400
750; Up-flow regeneration, take
450 1000. If the inlet water
hardness is higher, the factor is
smaller.
Resin volume, m
3
.
By hoursT1=Q÷Q
h
(Hour)
Average water consumption per hour (m
3
/h)
Water treatment capacity (m
3
)
By days: T1=Q÷Q
d
(Day)
Average water consumption per day (m
3
/d)
Water treatment capacity (m
3
)
Backwash Time T2
Generally, it is suggested to set 1015 minutes. The higher the
turbidity is, the longer backwash time shall be set. However, if the
turbidity is more than 5FTU, it is better to install a filter in front of the
exchanger.
Brine & Slow Rinse Time T3
T3=(4050)×H
R
(min)
Generally, T3=45H
R
(min)
In this formulaH
R
——The hight of the resin in the exchange tank (m)
Brine Tank Refill Time T4
Down flow regenerationT40.45×V
R
÷Brine refill speed
Up flow regenerationT40.34×V
R
÷Brine refill speed