EasyManuals Logo

Runxin N77A3 User Manual

Default Icon
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
MODEL: 63518-N77A1 /63618-N77A3/ 53518-N77B1
5
1.3. Service Condition
Runxin Valve should be used under the below conditions:
Requirement
Working
conditions
Water pressure
0.2MPa0.6MPa
Water temperature
5℃~50
Working
environment
Environment
temperature
5℃~50
Relative humidity
≤95%25
Electrical facility
AC100240V/5060Hz
Inlet water
quality
Water turbidity
Softener(N77A)5FTU
Filter(N77B)20FTU
Water hardness
First Grade Na
+
6.5mmol/L
Second Grade Na
+
10mmol/L
Free chlorine
0.1mg/L
Iron
2+
0.3mg/L
CODMn
2mg/L (O
2
)
In the above table, First Grade Na+ represents First Grade Na+
Exchanger. Second Grade Na+ represents Second Grade Na+
Exchanger.
When the water turbidity exceeds the conditions, a filter should be
installed on the inlet of control valve.
When the water hardness exceeds the conditions, the outlet water
hardness will hardly reach the requirement of boiler feed water0.03
mmol/L. It is suggested to adopt second grade softener.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Runxin N77A3 and is the answer not in the manual?

Runxin N77A3 Specifications

General IconGeneral
BrandRunxin
ModelN77A3
CategoryControl Unit
LanguageEnglish

Related product manuals