MODEL: 63518-N77A1 /63618-N77A3/ 53518-N77B1
14
2.2. Basic Setting & Usage
A. Parameter specification
Function
Indica
tor
Factory
Default
Parameter set
range
Instruction
Time of
Day
Random
00:0023:59
Set the time of day when use
flash.
Control
Mode
A-01
A-01
A-01
Regenerate on the day although
the available volume of treated
water drops to zero (0).
Regeneration starts at the
regeneration time.
A-02
Regenerate immediately when the
available volume of treated water
drops to zero(0).
A-03
Meter Delayed Regeneration type,
but by setting Resin Volume, Feed
Water Hardness, Regeneration
Factor, the controller will calculate
the System Capacity.
Regeneration mode same as
A-01.
A-04
Meter Immediately Regeneration
Type, but by setting Resin
Volume, Feed Water Hardness,
Regeneration Factor, the
controller will calculate the System
Capacity. Regeneration mode
same as A-02.
Service
Days
1-03D.
099 Days
Only for Time Clock Type,
regeneration by days
Service
Hours
1-20H.
099 Hours
Only for Time Clock Type,
regeneration by hours
Regener
ation
Time
02:00
02:00
00:0023:59
Regeneration time light on