18
Tubing
4.5 Line Set Installation (cont.)
4.0 INSTALLATION
4.5.2 Relative Location of Indoor and Outdoor Units
4.5.2.1 Outdoor Unit Level or Near Level to Indoor Coil Line Set
REFERENCE TABLE 2 FOR
MAXIMUM LENGTH LIMITATIONS
IDEALLY, LINE SET SLOPES AWAY
FROM OUTDOOR UNIT. VERIFY
SUB-COOLING PRIOR TO EXPANSION
DEVICE, INSULATED LIQUID LINE IN
UNCONDITIONED SPACE FOR
LONG LINE APPLICATIONS.
INSULATED VAPOR LINE FULL LENGTH
ST-A1345-06-00
Figure 3
For applications with the outdoor unit and indoor
unit on the same level the following is required:
• Insulated liquid line in unconditioned space only.
• Insulated vapor line full length.
• Vapor line should slope toward the indoor unit.
(Reference Figure 3)
• Follow the proper line sizing, maximum linear and
equivalent length, charging requirements, and oil
level adjustments spelled out in this document.
• Verify at least 5°F [2.8°C] sub-cooling at the in-
door unit prior to expansion device.