Light Commercial R410A on-off
S13-01.01.13en
6. Capacity Tables
SIB-60DAV
Cooling
Heating
Remark:
TC : Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input power ; kW
Indoor Units. HSP Duct Type
72
Heating Outdoor conditions
Indoor Conditions
(DB)
(kW)
24/18ºC
DB/WB
7/6ºC
DB/WB
2/1ºC
DB/WB
-5/-6ºC
DB/WB
-7/-8ºC
DB/WB
15ºC
TC
9.88 7.98 6.54 5.93 5.55
Input
2.54 2.19 1.88 1.76 1.67
20ºC
TC
9.58
7.60
6.16 5.78 5.32
Input
2.78
2.35
2.07 1.91 1.79
27ºC
TC
8.97 7.14 5.78 5.62 5.02
Input
2.94 2.54 2.24 2.07 1.93
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 18ºC 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 7.53 7.31 6.96 6.60 6.32
SC 5.49 5.41 5.36 5.28 5.31
Input 2.00 2.08 2.25 2.35 2.43
24/17ºC DB/WB
TC 7.74 7.53 7.17 6.82 6.39
SC 5.73 5.64 5.59 5.52 5.37
Input 2.13 2.20 2.35 2.45 2.58
27/19ºC DB/WB
TC 7.88 7.67 7.31 7.10 6.60
SC 5.75 5.67 5.63 5.54 5.41
Input 2.18 2.25 2.38 2.50 2.63
32/23ºC DB/WB
TC 8.09 7.81 7.53 7.38 6.82
SC 6.80 6.64 6.55 6.50 6.34
Input 2.28 2.35 2.45 2.63 2.73