SECTION 4 | Parameter Setup
4.7.2.4 CUT OFF VOLT 2 (Table 4.8, Parameter Setup Screen No.4)
If during "Charging Mode", the AC input voltage rises above "CUT-OFF VOLT 2" for period > "DETECT TIME 2", the
EVO™ Inverter/Charger will transfer to "Inverting Mode".
4.7.2.4.1 Programming Steps for Parameter "CUT OFF VOLT 2"
ð ð
E V O - 1 2 1 2 F I n v e r t i n g
A C o u t p u t : 1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
Enter Key Down Key x 3 times
Any Operating Mode Screen from
Fig 3.1 to 3.5
[Above screen is Screen 1 of Fig 3.2(a)]
Password 8052
See Section 4.3.1
See Table 4.8, Parameter Setup
Screen No. 4
for programmable range
S e l e c t G r o u p
* C H A R G E C U R V E
ð
S e l e c t P a r a m e t e r
* I N P U T H I G H L I M I T
ð
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* R E S E T V O L T A G E
1 2 5 . 0 V
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* C U T O F F V O L T 2
1 4 0 . 0 V
Down Key x 3 times
Enter Key
P a s s w o r d k e y i n
0 0 0 0
ð
Enter Key
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* C U T O F F V O L T 2
1 4 0 . 0 V
ð
Enter Key
4.7.2.5 DETECT TIME 2 (Table 4.8, Parameter Setup Screen No.5)
This is the time limit in cycles up to which high AC input voltage "CUT-OFF VOLT 2"is allowed.
4.7.2.5.1 Programming Steps for Parameter "DETECT TIME 2"
ð ð
E V O - 1 2 1 2 F I n v e r t i n g
A C o u t p u t : 1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
Enter Key Down Key x 4 times
Any Operating Mode Screen from
Fig 3.1 to 3.5
[Above screen is Screen 1 of Fig 3.2(a)]
Password 8052
See Section 4.3.1
See Table 4.8, Parameter Setup
Screen No. 5
for programmable range
S e l e c t G r o u p
* C H A R G E C U R V E
ð
S e l e c t P a r a m e t e r
* I N P U T H I G H L I M I T
ð
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* R E S E T V O L T A G E
1 2 5 . 0 V
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* D E T E C T T I M E 2
1 5 c y c l e
Down Key x 3 times
Enter Key
P a s s w o r d k e y i n
0 0 0 0
ð
Enter Key
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* D E T E C T T I M E 2
1 5 c y c l e
ð
Enter Key
4.7.2.6 CUT OFF VOLT 3 (Table 4.8, Parameter Setup Screen No.6)
If during "Charging Mode", the AC input voltage rises above "CUT-OFF VOLT 3" for period > "DETECT TIME 3", the
EVO™ Inverter/Charger will transfer to "Inverting Mode".
4.7.2.6.1 Programming Steps for Parameter "CUT OFF VOLT 3"
ð ð
E V O - 1 2 1 2 F I n v e r t i n g
A C o u t p u t : 1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
Enter Key Down Key x 5 times
Any Operating Mode Screen from
Fig 3.1 to 3.5
[Above screen is Screen 1 of Fig 3.2(a)]
Password 8052
See Section 4.3.1
See Table 4.8, Parameter Setup
Screen No. 6
for programmable range
S e l e c t G r o u p
* C H A R G E C U R V E
ð
S e l e c t P a r a m e t e r
* I N P U T H I G H L I M I T
ð
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* R E S E T V O L T A G E
1 2 5 . 0 V
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* C U T O F F V O L T 3
1 4 5 . 0 V
Down Key x 3 times
Enter Key
P a s s w o r d k e y i n
0 0 0 0
ð
Enter Key
S e l e c t P a r a m e t e r
I N P U T H I G H L I M I T
* C U T O F F V O L T 3
1 4 5 . 0 V
ð
Enter Key