11English
Installation Procedure
Main power terminal block specifications
• 1-phase terminal block specifications
1(L) 2(N)
F1 F2
LN
15 12 11.4
10.1
Main power cable specifications
The power cable is not supplied with air conditioner.
• Select the power supply cable in accordance with relevant local and national regulations.
• Wire size must comply with the applicable local and national code.
• Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Single phase
Indoor unit Outdoor unit Hz Volts Min. Max. Cooling Heating Indoor unit Total MCA MFA
AC036MN4PKH
AC036MXADKH
50/60 220-240 198 264 24 24 1.5 25.5 25.5 30
AC036MN4DKH
50/60 220-240 198 264 24 24 1.0 25.0 25.0 30
AC036MNCDKH
50/60 220-240 198 264 24 24 2.0 26.0 26.0 30
AC036MNMDKH
50/60 220-240 198 264 24 24 2.5 26.5 26.5 30
AC048MN4PKH
AC048MXADKH
50/60 220-240 198 264 32 32 1.5 33.5 33.5 40
AC048MN4DKH
50/60 220-240 198 264 32 32 1.0 33.0 33.0 40
AC048MNCDKH
50/60 220-240 198 264 32 32 2.0 34.0 34.0 40
AC048MNMDKH
50/60 220-240 198 264 32 32 2.5 34.5 34.5 40
AC054MN4DKH
AC054MXADKH
50/60 220-240 198 264 32 32 1.0 33.0 33.0 40
AC054MNCDKH
50/60 220-240 198 264 32 32 2.0 34.0 34.0 40
AC054MNMDKH
50/60 220-240 198 264 32 32 2.7 34.7 34.7 40
NOTE
1 Voltage range
• Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits
2 Maximum allowable voltage variation between
phases is 2%.
3 Wire size & type must comply with the applicable
local and national code.
• Wire size: Based on the value of MCA.
• Wire type: 60245 IEC57(IEC) or H05RN-
F(CENELEC) grade or more.
4 MFA is used to select the circuit breaker and the
ground fault circuit interrupter (earth leakage circuit
breaker).
5 MCA represents maximum input current.
• MFA represents capacity which may accept MCA
• Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)