EasyManua.ls Logo

Samsung AC MXADKH Series - Step 5: Connecting the Refrigerant Pipe

Samsung AC MXADKH Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15English
Installation Procedure
Step 5 Connecting the refrigerant pipe
Items
Maximum allowable length
Single installation
DPM
installation
Applicable outdoor unit models
AC026MXADKH
AC035MXADKH
AC052MXADKH
AC060MXADKH
AC052MXASEH
AC071MXADKH
AC071MXASEH
AC100MXASEH
AC071MXADKH
Total pipe length (L
1
+L
2
+L
3
)
- - - 50m
Main pipe (L
1
)
20m 30m 50m 30m
Max. distance among indoor units (D)
- - - 10m
Max. length after branch
- - - 15m
Max. height difference between outdoor
and indoor units (h
1
)
15m 20m 30m ±30m
Max. height difference among indoor
units(h
2
)
- - - ±0.5m
Max Pipe length difference among indoor
units after branch (L
2
-L
3
)
- - - ±5m
“n” means the number of indoor unit connection of DPM.
Use a joint kit that is only for DPM.