01 PREPARATION
English-11
11.81 or
more
11.81 or more 23.62 or more 23.62 or more 23.62 or more
❋ When 3 sides of the outdoor unit are blocked by the wall
11.81 or
more
59.06 or more
23.62 or more
23.62 or more
❋ When front and rear side of the outdoor unit is towards the wall
59.06 or more 23.62 or more 118.11 or more 7.87 or more118.11 or more
❋ When 3 sides of the outdoor unit are blocked by the wall
t The units must be installed according to distances declared, in order to permit accessibility from each side, either
to guarantee correct operation of maintenance or repairing products.
The unit’s parts must be reachable and removable completely under safety condition (for people or things).
CAUTION
t Should adopt bar type louver. Don’t use a type of rain resistance louver.
t Louver specifications.
– Angle criteria : less than 20˚
– Opening ratio criteria : greater than 80%
WARNING
[Bar type louver]
[Rain resistance louver]
19.69 or more19.69 or more
11.81 or more
11.81 or more
❋ The upper part of the outdoor unit
and the air outlet is towards the wall