01 PREPARATION
English-13
Connecting the cable
Two electronic cables must be connected to the outdoor unit.
f The connection cord between indoor unit and outdoor unit.
f The power cable between outdoor unit and auxiliary circuit breaker.
f Be sure to run the power supply cable and the communication cable through
electrical conduit as seen in the picture.
f Protect the power and communication cable using the protection tube
individually.
f Make a knockout hole.
f After making a knockout hole, apply rust resisting paint around the hole.
f Secure the cable tube to the outdoor knockout using the CD connector and
bushing.
t During the unit installation make rst refrigerant connections and then
electrical connections. If unit is uninstalled rst disconnect electrical
cables, then refrigerant connections.
t Connect the air conditioner to grounding system before performing
the electrical connection.
t When installing the unit, you shouldn't use inter connection wire.
CAUTION
Conduit
Example of Air Conditioner System
When using ELCB for 1 phase
ELCB
1
Indoor Unit
Power cable
Outdoor Unit
Communication cable
Grounding
OR
Power cable
Communication cable
Power Cable Specications
f The power cable is not supplied with air conditioner.
- Select the power supply cable in accordance with relevant local and national regulations.
- Wire size must comply with the applicable local and national code.
- Specications for local wiring power cord and branch wiring are in compliance with local cord.
Model
Power Source RLA
FLA
MCA MOP
Outdoor Indoor Outdoor Indoor
AC018MXSCCC/AA AC018MNADCH/AA 208~230V/60Hz 9.0 A 0.9 A 0.7 A 13.0 15.0
AC024MXSCCC/AA AC024MNADCH/AA 208~230V/60Hz 10.5 A 0.9 A 0.7 A 16.0 20.0