Short
push
Display contents SEG1 SEG2 SEG3 SEG4 Unit
13 Protective control D
0: Cooling
1: Heating
Protective control
0: No Protective control
1: Freezing
2: Non-stop defrosting
3: Over-load
4: Discharge
5: Total electric current
Frequency status
0: Normal
1: Hold
2: Down
3: Up_limit
4: Down_limit
-
14
The temperature of heat radiating
plate
E Hundreds' digit Tens' digit Unit digit -
15 S/W check F - - - -
Long push 1 Main micom version Year (Hex) Month (Hex) Date (Tens' digit) Date (Unit digit)
After short push 1 Inverter micom version Year (Hex) Month (Hex) Date (Tens' digit) Date (Unit digit)
After short push 1 E2P version Year (Hex) Month (Hex) Date (Tens' digit) Date (Unit digit)
After short push 1
Display automatically assigned address (communication address) of the unit
Page1 -AUTO
Page2 - (SEG1,2 - Indoor unit: "A","0")(SEG3,4 - Address: ex) 00)
After short push 1
Display manually assigned address of the unit
Page1 -MANU
Page2 - (SEG1,2 - Indoor unit: "A","0")(SEG3,4 - Address: ex) 00)
❋ Long push K4(Main micom ver.) short push 1 more(Inv. micom ver.) short push 1 more(E2P. ver.)
7. DIP switch option
On (default) O
1234
ON
Switch 2 Disable snow prevention control Enable snow prevention control
Switch 3
Silence Mode option
Switch 4
❋ When snow prevention mode is in use, eco mode(standby mode)will not be functional.
8. Silence Mode DIP switch option
Switch 3 Switch 4 Operation
On On Disable Silence mode
On O Silence mode 1st step
O On Silence mode 2nd step
O O Silence mode 3rd step
02 INSTALLATION
English-29