Installation Procedure
6 View mode: When the K4 switch is pressed, you can see information about our system state as below.
For a function that is not supported, "-" is shown for SEG2, SEG3 or SEG4.
K4 short push Display contents SEG1 SEG2 SEG3 SEG4 Unit
1 Order frequency 1 Hundreds digit Tens digit Units digit Hz
2 Current frequency 2 Hundreds digit Tens digit Units digit Hz
3
The number of preset indoor
units
3 Hundreds digit Tens digit Units digit EA
4 Ambient temperature sensor 4
Hundreds digit
or "-"
¹⁾
Tens digit Units digit
℃ or
²⁾
5 Compressor discharge sensor 5
Hundreds digit
Tens digit Units digit
℃ or
²⁾
6 Eva-Mid sensor 6
Hundreds digit
or "-"
¹⁾
Tens digit Units digit
℃ or
²⁾
7 Condensor sensor 7
Hundreds digit
or "-"
¹⁾
Tens digit Units digit
℃ or
²⁾
8 Current 8 Tens digit Units digit
The first place of
decimals
A
9 Outdoor fan RPM 9 Thousands digit Hundreds digit Tens digit rpm
10 Target discharge temperature A
Hundreds digit
or "-"
¹⁾
Tens digit Units digit
℃ or
²⁾
11 EEV B Hundreds digit Tens digit Units digit step
12
The capacity sum of indoor
units
C Tens digit Unit digit
The first place of
decimals
kW or
kBtu/h
³⁾
13 Protective control D
0: Cooling
1: Heating
Protective control
0: No Protective control
1: Freezing
2: Non-stop defrosting
3: Over-load
4: Discharge
5: Total electric current
Frequency status
0: Normal
1: Hold
2: Down
3: Up_limit
4: Down_limit
-
14 IPM temperature E
Hundreds digit
or "-"
¹⁾
Tens digit Units digit
℃ or
²⁾
15
The number of connected
indoor units
F Hundreds digit Tens digit Units digit EA
16 ESC EEV(CAM) G Hundreds digit Tens digit Units digit step
17 ESC IN sensor H
Hundreds digit
or "-"
¹⁾
Tens digit Units digit
℃ or
²⁾
18 ESC OUT sensor I
Hundreds digit
or "-"
¹⁾
Tens digit Units digit
℃ or
²⁾
19 View mode end BLANK BLANK BLANK BLANK
¹⁾ Sub-zero temperatures are expressed as a minus, instead of hundreds digit.
²⁾ The temperature unit can be switched between Celsius and Fahrenheit through Setting outdoor unit option switches.
(Default value is Celsius.)
³⁾ If the temperature unit is set to Fahrenheit through Setting outdoor unit option switches, the value is expressed in the
unit of kBtu/h.
DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 29DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 29 2021-09-14 오전 9:22:012021-09-14 오전 9:22:01