EasyManua.ls Logo

Samsung AC024KNZDCH/AA - Page 45

Samsung AC024KNZDCH/AA
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Capacity Correction
Outdoor Units
Pipe Length (ft)
:
:<H>
32.8 49.2 65.6 82.0 98.4 114.8 131.2 147.6 164.0
Level Difference (ft)
98.4 -----0.940.930.920.910.90
82.0 ----0.960.940.930.920.910.90
65.6 - - - 0.97 0.96 0.94 0.93 0.92 0.91 0.90
49.2 - - 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
32.8 - 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
16.4 1.00 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
0.0 1.00 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
-16.4 1.00 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.90 0.88
-32.8 - 0.98 0.97 0.96 0.95 0.94 0.92 0.91 0.89 0.87
-49.2 - - 0.97 0.96 0.94 0.93 0.92 0.90 0.88 0.85
-65.6 - - - 0.95 0.94 0.93 0.91 0.89 0.87 0.83
-82.0 ----0.940.920.910.890.860.82
-98.4 -----0.920.900.880.850.80
Heating
Pipe Length (ft)
:
:<H>
32.8 49.2 65.6 82.0 98.4 114.8 131.2 147.6 164.0
Level Difference (ft)
98.4 -----0.940.930.920.910.90
82.0 ----0.960.940.930.920.910.90
65.6 - - - 0.97 0.96 0.94 0.93 0.92 0.91 0.90
49.2 - - 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
32.8 - 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
16.4 1.00 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
0.0 1.00 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
-16.4 1.00 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
-32.8 - 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
-49.2 - - 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
-65.6 - - - 0.97 0.96 0.94 0.93 0.92 0.91 0.90
-82.0 ----0.960.940.930.920.910.90
-98.4 -----0.940.930.920.910.90
9@BS89@BMTW9@S89@MT
:<BS8:<BMTW:<S8:<MT
;8BS8;8BMTW;8S8;8MT
Cooling

Other manuals for Samsung AC024KNZDCH/AA

Related product manuals