EasyManua.ls Logo

Samsung AF28FVSDA N Series - When Error Code between Main ↔ Panel Is Indicated on the Indoor Temperature Display Area

Samsung AF28FVSDA N Series
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-11
4-4-2 When error code " " between main panel is indicated on the indoor temperature
display area
1. Cause of malfunction
1) Disconnected or loosely connected main panel connection wire
2) Faulty indoor unit Main PBA
3) Faulty Panel PBA
2. Check procedure
Replace faulty Panel PBA
Re-inspect connection of main
panel PBA wire
Connect Panel PBA and Main PBA
Inspect or replace connector wire
No
Yes
Yes
No
When measuring
numbers 2-3, 2-4 pin test of Panel PBA CN30,
does it fluctuate (during communications)
between DC3V~DC5V?
Is the connection wire
between the main Panel PBA disconnected
or loosely connected?
<Measure voltage>
Turn on the main power switch.

Table of Contents

Related product manuals