Installation Procedure
1 Before supplying the power, use DC 500V (AM****XV*J*)
or DC 600 V (AM****XV*F*) insulation resistance tester to
measure the power (3 phase: R, S, T/ 1 phase: L, N) terminal
and the outdoor unit grounding.
đʪɇϑЇθʪʪϩϑ˵ͱЇʒɵʪͱЭʪθߥߢđצ࢏
2 Before supplying the power, use a voltmeter and phase tester
to check the voltage and the phase.
R, S, T terminal: Check the 460V (AM****XV*J*) or 230V
(AM****XV*F*) between wires (R-S, S-T,
T-R)
CAUTION
Never measure the communication terminal since
communication circuit may get damaged.
Check for short-circuit of the communication terminal with a
general circuit tester.
T
S
R
< ELB >
[AM****XV*J*]
460V
460V
460V
T
S
R
[AM****XV*F*]
< ELB >
230V
230V
230V
3 Check if the R-410A indoor units are connected.
4 When N phase is not correctly connected to R, S and T phase,
over-voltage protection control will be in effect and it will cut-
off the power of the PCB. Check the power cable connection of
the N phase if the PCB is not turned on.
5 Check the following after the installation is completed.
Performing final checks and trial operation
Installation work
Outdoor unit
Have you checked the external surface and the inside of the outdoor unit?
Is there any possibility of short-circuit caused by the heat of an outdoor unit?
Is the place well-ventilated and ensures space for service?
Is the outdoor unit fixed securely to withstand any external force?
Indoor unit
Have you checked the external surface and the inside of the indoor unit?
Is there enough space for service?
Have you checked if the center of the indoor unit is ensured and it is installed horizontally?
Refrigerant pipe work
Have you selected correct pipes?
Are the liquid and gas valve open?
Is the total number of connected indoor units within the allowable range?
Are the length and the height difference between the refrigerant pipes within the allowable range?
Are the branch joints properly installed?
Did you check the connection of liquid and gas pipes?
Have you selected correct insulator for pipes and insulated them correctly?
Did you insulate the pipes and connection part correctly?
Is the quantity of the additional refrigerant correctly weighed in? (You must record the amount of
additional refrigerant on the service record paper placed inside of the outdoor unit.)
Drain pipe work
Have you checked if the drain pipes of the indoor and outdoor unit are connected together?
Have you completed the drain test?
Is the drain pipe properly insulated?
Electrical wiring work
Are the power cable and communication cable tightened firmly on the terminal board within the
range of rated tightening torque?
Have you checked for cross-connection of the power and communication cables?
Have you performed the earthing work 3 to the outdoor unit?
Did you make sure to use 2-core cable (not multi-core cable) for the communication cable?
Is the length of the wire within allowed range?
Is the wiring route correct?
Setting address
Did you set the address of the indoor and outdoor units properly?
Did you set the address of the indoor and outdoor units properly? (When using multiple remote
controllers)
Option
If there is a possibility of the outdoor unit from vibrating, check whether the anti-vibration frame is
correctly installed.