55
English
Installation manual
Option
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
Heating
(When setting SEG3)
Time required for
mode change
Compensation option
for Long pipe or height
difference between indoor
units
MTFC (*3) -
Indication
and Details
Indication
Details Indication Details Indication Details Indication Details
Indication Details
1
0 1°C 0 5 min. 0
Default
0
Default
1 1.5°C 1 7 min.
1
(*1) Height
difference is
more than
30m or (*2)
Distance is
longer than
110m
2 2°C 2 9 min.
3 2.5°C 3 11 min.
4 3°C 4 13 min.
2
(*1) Height
difference is
15~30m or
(*2) Distance
is 50~110m
2 Use
5 3.5°C 5 15 min.
6 4°C 6 20 min.
7 4.5°C 7 30 min.
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation - -
Dual fuel (heater lock)
setting
Dual fuel (HP lock)
setting
-
Control variables when using hot water / external heater
(*4)
Indication
and Details
Indication Details - Indication Detail Indication Detail - Indication
Details
0 Disuse
2 -
0 Disuse 0 Disuse
-
0
At the same
time as
thermo on
No delay
1 1 1
At the same
time as
thermo on
10 minutes
2 2 2
At the same
time as
thermo on
20 minutes
3 3 3 1.5 °C No delay
4 4 4 1.5 °C 10 minutes
5 5 5 1.5 °C 20 minutes
6 6 6 3.0 °C No delay
7 7 7 3.0 °C 10 minutes
8 8 8 3.0 °C 20 minutes
9 9 9 4.5 °C No delay
A A A 4.5 °C 10 minutes
B B B 4.5 °C 20 minutes
C C C 6.0 °C No delay
D D D 6.0 °C 10 minutes
E E
E 6.0 °C 20 minutes
F
Cannot be
used
F
Cannot be
used